DKAC-I / MBAC-I
- Climate gateway
Programming manual
v1.0
www.besknx.com
6
5
Mode
Mode status: 0=Auto; 1=Heat;
3=Cool; 9=Fan; 14=Dry
1 byte
C R -
T -
6
Fan
Fan: 0-50%=Low; 51-
100%=High
1 byte
C - W - U percentage
(0..100%)
7
Fan
Fan status: 0-50%=Low; 51-
100%=High
1 byte
C R -
T - percentage
(0..100%)
8
Temperature Temperature: Received from
machine
2 bytes
C R -
T - temperature
(°C)
10
Window
Open window: 0=Close; 1=Open 1 bit
C - W - U
12
Swing
Swing: 0=Fixed position;
1=Motion
1 bit
C - W - U switch
13
Swing
Swing status: 0=Fixed position;
1=Motion
1 bit
C R -
T - switch
14
Swing
Swing: 0-80%= Fixed position;
100%=Motion
1 byte
C - W - U percentage
(0..100%)
15
Swing
Swing status: 0-80%=Fixed
position; 100%=Motion
1 byte
C R -
T - percentage
(0..100%)
16
Internal
ERROR
Internal ERROR: 0=No
error;1=Error
1 bit
C R -
T - boolean
18
External
ERROR
External ERROR: 0=No error;
1=Error
1 bit
C R -
T - boolean
19
External
ERROR
External ERROR: Type
1 byte
C R -
T - ratio (0..255)
102
Scenes
Scenes
1 byte
C - W - U scene control
103
Mode
Mode: 0=Cool; 1=Heat
1 bit
C - W - U switch
104
Mode
Mode status: 0=Cool; 1=Heat
1 bit
C R -
T - switch
105
Fan
Fan: 0-33%=Min; 34-
67%=Med; >68%=High
1 byte
C - W - U percentage
(0..100%)
106
Fan
Fan status: 0-33%=Min; 34-
67%=Med; >68%=High
1 byte
C R -
T - percentage
(0..100%)
21
Mode
Cool: 1=Set mode; 0=No
effect
1 bit
C - W - U switch
22
Mode
Heat: 1=Set mode; 0=No
effect
1 bit
C - W - U switch
23
Mode
Fan: 1=Set mode; 0=No effect 1 bit
C - W - U switch
24
Mode
Dry: 1=Set mode; 0=No effect 1 bit
C - W - U switch
25
Mode
Auto status: 1=Set; 0=Not set 1 bit
C R -
T - enable
26
Mode
Cool status: 1=Set; 0=Not set 1 bit
C R -
T - enable
27
Mode
Heat status: 1=Set; 0=Not set 1 bit
C R -
T - enable
28
Mode
Fan status: 1=Set; 0=Not set
1 bit
C R -
T - enable
29
Mode
Dry status: 1=Set; 0=Not set
1 bit
C R -
T - enable