13.4 Testing the senders and analog inputs
A) -
Push the [ACK-F10] pushbutton, for about 10 seconds, until the message [SEnS] appears.
B) -
Apply 3 resistors of known value (+/- 1%) in a range 100 Ohm up to 1000 Ohm as indicated in section 13.1.
C) -
Push the pushbuttons according to the
Table 13.4.
You should read the value in OHM on the display. The
display indicates the reading as long as you push and hold the button. If the value indicated by the display is
more than 3% (or less than 3%), the Be42 is damaged and should be returned for service.
You can apply Voltages and Current in order to verify the performance of the controller. Apply signals as closer
as you can to „Recommended range‟ (see the table below)
Table 13.4: Senders and Analog inputs true table
Pushbutton
Display
Code (°)
Terminal
number
Function
Recommended
range
[I-F5]
[XXXX]
# 26
Fuel Level Sensor
100-1000 Ohm
[O-F4]
[XXXX]
# 27
Temperature Sensor
100-1000 Ohm
[I-F3]
[XXXX]
# 28
Oil Pressure Sensor
100-1000 Ohm
[START]
[UXXX]
#13-15
Voltage of the Generator
400Vac
[AUTO]
[MXXXX]
#16-18-20
Voltage of the Mains
400Vac
[MAN]
[cXX.X]
#21-22
Voltage of the charger Alternator
10-24 VDC
[OFF]
[bXX.X]
#23-24
Voltage of the Battery
10-24 VDC
[←F8]
[GXX.X]
#13-15
Frequency of the Generator
50Hz
[F9→]
[MXX.X]
#16-18-20
Frequency of the Mains
50Hz
[STOP]
[XXXX]
#11-12
Current of the Generator
100A
(°)Note. [XXXX] indicates a 4 digit number.
Note: If readings are /- 3% tolerance, the Be42 is working well. You can increase the precision by using
the calibration (see section 12.0). If the readings are o / - 3% tolerance, the Be42 is damaged and
should be returned for service.
To exit the Troubleshooting, remove the Vdc supply at anytime
Section 14.0 General Specifications
Supply Voltage [***]:
4.5Vdc to 36Vdc.
Protection:
internal 300mA thermal fuse.
Supply Current:
50 mA up to 150mA
Non repetitive Supply Over Voltage [@ 100ms]:
80Vdc ,
[@ 10ms] :
200Vdc (a 1A fuse fast must be provided in series to
the power supply terminal #24. It must blow within 300ms at 1A current).
Dimensions:
224mm X 105mm X 68mm,
Panel Cut-out:
190mm X 93mm, indoor operation
Operating Temperature range:
-30 deg C up to +70 deg C.
Humidity Range:
5% up to 95% non-condensing.
Weight:
850 gr.,
Vibration:
40mm/sec
General Design:
89/336 EEC, 89/392 EEC, 73/23 EEC, 93/68 EEC, IEC 68-2-6
Certification:
CE
Static Output Characteristics
Output Current: 300mA/100Vdc (internal AUTO-reset 700mA Fuse is provided). Logic: negative.
Mains and Generator Voltage Input
Nominal Voltage input: 70 Vac up to 600Vac
Over voltage admitted: 4KVac for one second. Measurement precision: +/- 2%
[**]
. Input impedance: 2 Mega Ohm
Current Transformer Input
Size: 10/5Aac up to 2000/5Aac. Maximum Over Current: 8Aac for 30 seconds.
Measurement precision: +/- 2%
[**]
. Internal resistance: 0.05 Ohm
Digital /Analog Inputs
Open circuit voltage: 10Vdc (12V supply) or 22Vdc (24V supply) - Closed circuit current: 15mAdc maximum.
Trigger level for digital inputs: < 2Vdc.
Charger Alternator Monitoring
Operating Voltage up to 36Vdc. Vdc reading ac/- 5%. Excitation Power: max 3W
[*]
NOTE: the sum of the total output current (# 1- # 10)may not exceed 2A at 70°C
[**]
NOTE: errors can be reduced by using the calibration mode (section 12.0)
[***]
NOTE: operations with memory (storing parameters, hours, etc) are allowed only if the Vdc is over 11.5V.