Be42 OEM's Manual V5.0.XX - December - 2010 page 12
12
Table
7.01A - Mains Failure Control
Note: [ xx " ] = seconds, [ xx ' ] = minutes, [xxh ] = hours
Parameter Code & Description
Default
Min
Max
P.0 Mains Contactor control (KM).
If the Mains Failure persists for more than [P.0]
(seconds or minutes), the Mains contactor will open and the [P.1] timer will start to
count. The Mains contactor will close only after the [P.2] timing.
[ 5‟‟]
0
59mins
P.1 Mains Failure time.
After the [P.0] timing (see above), the engine will start if the
Mains Failure persists for the [P.1] time.
[ 5‟‟]
0
23h
P.2 Mains Restore time.
The Be42 transfers the Load to the Mains once the MAINS is
stable for at least [P.2] (seconds, minutes or hours) . During [P.2] , the engine will
continue to run ON-LOAD. After [P.2], the [P.24] timer will take place to run the engine
OFF-LOAD (the contactor of the generator will open)
[ 5‟‟]
0
23h
Table
7.01B - Mains Failure Control
Note: [ xx " ] = seconds, [ xx ' ] = minutes, [ oFF ] = disabled
Parameter Code & Description
Default
Min
Max
Options
P.3 Contactors changeover.
This timing introduces a delay
between the switching of the contactors.
[ 2‟‟]
0.1secs 15.0secs
-
P.4 Under voltage limit.
If the Phase-to-Phase voltage falls
under this limit, the [P.0] timer will energize.
[320]
60V
998V
[oFF]
P.5 Over voltage limit.
If the Phase-to-Phase voltage rises
above the limit, the [P.0] timer will energise
.
[500]
60V
998V
[oFF]
P.6 Under Hz limit.
If the Phase-to-Phase frequency falls
under the limit, the [P.0] timer will energize.
[47.0]
20.0Hz
70.0Hz
[oFF]
P.7 Over Hz limit.
If the Phase-to-Phase frequency rises
above the limit, the [P.0] timer will energise
.
[53.0]
20.0Hz
70.0Hz
[oFF]
P.8 Phase Selection.
It allows 3-Phase or Single Phase control
(see section 16.30).
[3-P]
-
-
[3-P] [Ph-]