
Be242 Be242RB OEM's Manual V3.X.XX -
January - 2021 page 18
18
Section 8.0 - Alarms, Warnings and Shutdowns
The Be242 features Shutdowns (the engine stops) and Warnings (the engine will continue to run) and provides:
A)
- a general indication of alarm presence by means of the message [ALAr.] on the display
B)
- 4 configurable outputs for specific alarm indication with more than 40 options (see 7.08 and 7.09)
C)
- symbols on the front panel to indicate the most important alarms
D)
- display messages indicating warnings and shutdowns (see Table 4.1)
E)
- a pushbutton to silence the Horn ([ACK-F10])
Terminal #6 is pre-configured for HORN output (Option 39). A HORN should be externally provided. To silence
the HORN, push the [ACK-F10] pushbutton or wait for the
[P.50]
to expire (see section 7.05). If the
[P.50]
is set
to
[OFF]
, the only way to silence the Horn is by means of the [ACK-F10] pushbutton.
To browse the alarm memory push the [→F9] pushbutton. To display alarm details, push the [←F8] pushbutton.
To clear the alarm from the panel, remove the cause of the alarm and then press the [OFF] pushbutton. Table
4.10 in the section 4.0 indicates all alarms.
Section 9.0 Hour Meter
To clear or pre-load the counter, use the following instructions:
1) -
Enter the programming mode as indicated in sections 6.10 & 6.20
2) -
Select the parameter [P.51] by means of the [←F8] or [F9→] pushbutton.
3) -
Press the [START-
F1] and [TEST ↑] to set a value. If you set [0], you will cancel the [h-counter]. If you set a
value between 1 and 50000, you will pre-set the counter. Follow steps 4A) or 4B) according to your needs.
4A) -
Press and hold the [ACK-
F10] and [F9→] pushbuttons simultaneously until the [SaVE] message appears
(for about 5 seconds); the Be242 saves the hour counter in the memory and will enter the OFF mode.
4B) -
Press the [OFF] pushbutton to exit the procedure without modifying the counter.
Section 10.0 Be42 for PUMP SETS
If you use the Be242 to control a PUMP SET, we recommend the use of the following settings:
Parameter
Table 10.0: Recommended settings setup
[P.15]
[oFF]
(This disables the 'alternator failure alarm')
[Inp.4]
[ 15 ]
(This selects the Mains Simulation input mode). Connect a switch (or level switch) to
terminal #14 in order to control the set by remote
[P.41]
[oFF]
(This disables the Periodic Test interval)
[P.0]
[ 0 ]
(This disables the Breaker delay time)
[P.1]
According to your needs; the engine will start after a delay
[P.2]
According to your needs; the engine will stop after a delay