Table 7.02A - GENERATOR PARAMETERS     

Note: [  xx " ] = seconds, [  xx ' ] = minutes, [ oFF ] = disabled

 

Parameter Code & Description 

 Mode

 (°)

 

Default 

Min 

Max 

Options

 

 

P.9  Under voltage (Push F1)    

 

xxxxxxxxxxxxxxxxx 

 

 

[320] 

60 V 

998 V 

[oFF] 

Delay (Push F2)    

[  6" ] 

1 sec 

15 secs 

P.10  Over voltage (Push F1)    

 

[500] 

60 V 

998 V 

[oFF] 

Delay (Push F2)    

[   2" ] 

1 sec 

15 secs 

P.11  Under Hz (Push F1)    

 

[47.0] 

20.0 Hz 

70.0 Hz 

[oFF] 

Delay (Push F2)    

[  6'' ] 

1 sec 

15 secs 

P.12  Over Hz (Push F1)    

 

[53.0] 

20.0 Hz 

70.0 Hz 

[oFF] 

Delay (Push F2)    

[   1" ] 

1 sec 

15 secs 

P.13 

(*) 

Current limit Warning (Push F1)    

 

[oFF] 

10 A 

999 A 

[oFF] 

Delay (Push F2)    

[  1" ] 

1 sec 

15 mins 

P.14 

(*) 

Over current shut down (Push F1)    

 

[oFF] 

10 A 

999 A 

[oFF] 

Delay  (Push F2)    

[  1" ] 

1 sec 

15 mins 

 
(°) Mode1: 

The engine shuts down after a cooling down time ([P.24]). 

(°) Mode2: 

The engine shuts down without a cooling down time. 

(°) Mode3: 

The Be242 provides a warning if the parameters rise above the setting for the specified timing.

 

(*) 

The setting is allowed in step of 5 Amps by using the pushbutton on Be242 or in step of 1Amp by using programming by Computer. 

 

NOTE: WHEN VOLTAGE OR FREQUENCY IS OUTSIDE LIMITS, THE GREEN INDICATORS BLINKS SLOWLY. 

VOLTAGE MAY BE PRESENT INTO THE CONTROLLER EVEN IN CASE THE INDICATORS ARE OFF

 

 

Table 7.02B - GENERATOR PARAMETERS                    

 Note: [ oFF ] = disabled, [ on ] = enabled

 

Parameter Code & Description 

Default 

Min 

Max 

Options

 

 

P.15  Alternator failure options. 

The alarm [E04] energizes if the 

voltage (or the frequency) is lower than the setting of P.9 (or 
P11) for more than 150 seconds.

  

[oFF] 

[on] [oFF] 

P.16  Alternator number of Poles.

 

Options [2] or [4] allow you to 

display the engine speed.

 

[ 4 ] 

P.17  Generator Contactor Control.

 

The option [off] inhibits Load 

transfer to the generator in TEST  mode (or remote TEST) 
when MAINS is present.

 

[oFF] 

[on] [oFF] 

P.18  CT size (/5Aac). 

[100] 

50 A 

1000 A 

 
 
 
 
 
 
 

Содержание Be242 AMF ATS

Страница 1: ...o extra charge The buyer shall provide sufficient information on any alleged defects in the product so as to enable BD to determine their cause and existence If the Be242 is not defective or the produ...

Страница 2: ...LEDs 5 0 2 21 2 3 Lamp Test 5 1 Lo U Under Voltage 7 02A P 09 Lock Remote Lock E03 4 10 Low Battery voltage 4 10 Er 13 Log Events 4 30 Mains Failure 7 01A P 01 Mains Restore 7 01B P 02 Maintenance tim...

Страница 3: ...lt settings page 10 6 30 Reading the parameters page 10 6 40 Activating the password page 11 6 50 Changing the password page 11 6 60 Removing the password page 11 7 0 Programmable Param tre page 11 Ta...

Страница 4: ...of the software example 1 0 01 and the detected kind of battery 12V or 24V Should the battery supply to be lower than 7 5V the BE242 will trigger the ER 13 alarm code the software will not run The mo...

Страница 5: ...ned off and a dot on the display will blink slowly Push one of the pushbuttons on the front panel to activate the display 2 2 MANUAL mode Note default programming for emergency input is normally close...

Страница 6: ...ts the green indicator V blinks slowly see table 7 01 7 02 2 4 TEST mode Push the TEST pushbutton until the green LED illuminates The Be242 starts the engine and transfers the load to the Generator if...

Страница 7: ...age of the Mains 60 V up to 998 V If the Mains is simulated the display will show the message n on nXXX V R S XXX V S T _XXX L R T F8 or F9 U on ACK F10 Generator Frequency 20Hz up to 70Hz GXXX Hz F8...

Страница 8: ...ameter P 34 section 7 table 7 04 InP 3 Input 3 Shutdown Warning see 7 07 Er 08 Emergency Shutdown see parameter P 35 section 7 table 7 04 InP 4 Input 4 Shutdown Warning see 7 07 Er 09 Emergency Shutdo...

Страница 9: ...ed 6 10 Enter the Programming Mode 1 Provide a voltage from a battery supply of over 11 5 V Push the OFF F7 pushbutton to enter the OFF mode the LEDs and display turn OFF the dot on the right side of...

Страница 10: ...nter the OFF mode without saving the parameters You can select a mode of operation as indicated in section 2 0 6 20 Re programming Default settings The parameters of the Be242 are programmed in factor...

Страница 11: ...F9 pushbuttons simultaneously until the SAVE message appears approximately 5 seconds the Be242 saves the password and remains in PROGRAM mode To exit push the OFF pushbutton 6 60 Removing the passwor...

Страница 12: ...de Description Default Min Max Options P 3 Contactors changeover This timing introduces a delay between the switching of the contactors 2 0 1secs 15 0secs P 4 Under voltage limit If the Phase to Phase...

Страница 13: ...own without a cooling down time Mode3 The Be242 provides a warning if the parameters rise above the setting for the specified timing The setting is allowed in step of 5 Amps by using the pushbutton on...

Страница 14: ...Engine Cooling time 15 0 59 mins P 25 Stop Solenoid timing Energized to stop 15 1 sec 59 mins P 26 Alternator Crank termination Push F1 8 0 3 0 V 30 0 V oFF Belt break setting Push F2 8 0 3 0 V 30 0 V...

Страница 15: ...oFF disabled Parameter Code Description Default Min Max Options P 40 EJP time 5 1 sec 99 mins P 41 Periodic Test interval see 16 10 oFF 2 hours 9999 h oFF P 42 Periodic Test duration see 16 10 5 1 mi...

Страница 16: ...ooling and Stop 17 Horn silence 4 Bypass Cooling and Stop 18 Display Right Pushbutton 5 Warning only 19 Display Left Pushbutton 6 Bypass and Warning 20 Overload Input Warning 7 Remote Manual Mode 21 O...

Страница 17: ...tatus 14 NOT USED 46 Pre glow MODE 1 2 3 4 15 Low Battery Voltage Warning 47 NOT USED 16 High Battery Voltage Warning 48 RENT 48h 17 Low Fuel Shutdown switch 49 RENT 0h Expired 18 NOT USED 50 Engine R...

Страница 18: ...tes all alarms Section 9 0 Hour Meter To clear or pre load the counter use the following instructions 1 Enter the programming mode as indicated in sections 6 10 6 20 2 Select the parameter P 51 by mea...

Страница 19: ...otection This is accomplished by programming a voltage setting in the P 26 sub menu To test the efficiency of this protection disconnect terminal D from the charger alternator and connect to ground th...

Страница 20: ...nt panel one by one The display will show a message according to Table 13 1 As soon as you release all buttons the message will be displayed Table 13 1 Pushbuttons true table Pushbutton Display Code P...

Страница 21: ...ement Precision Vdc 1 Dimensions 224X105 X 68 mm Cut out round 56mm min Be242RB Dim 195X126 X 70 mm Rail mount Operating Temperature range 30 deg C up to 70 deg C Humidity Range 5 up to 95 non condens...

Страница 22: ...mmend that you program the P 31 to 15 number of attempts in order to provide proper time for AUTOSTART to start the engine 16 30 Single Phase operation Program the parameter P 8 with the option 3 as i...

Страница 23: ...o the AC1 rating of the contactors and according to the size of cables and terminal blocks In case of short circuit when the automatic protections fail you can trust to an additional external overcurr...

Страница 24: ...Be242 Be242RB OEM s Manual V3 X XX January 2021 page 24 24...

Страница 25: ...18 Current Trasf 2 22 L1 Generator 3 Start Solenoid 11 Low Oil Pressure 19 Current Trasf 3 24 L1 Generator 4 Stop Solenoid 12 High Temperature 20 Common CTs 24 KG Output 5 Output 2 13 Input 2 JC SUB...

Отзывы: