S
ERIES
DECO-TUBE
38
A
PRIL
/25/2013
Maintenance & Trouble Shooting
Trouble shooting continued…
Burner Does Not Light
Is spark visible through site glass during ignition trial? If no, further electrical checks by a
qualified service person are required.
Check to see if gas lines were properly purged of air.
Check inlet and outlet gas pressure during ignition period.
Check for proper orifice and air plate.
Burner Does Not Stay Lit
Check ground wire continuity.
Check insulation on the igniter leads.
Measure flame signal current; it should be between 2 to 6 micro amps dc. Minimum 0.8
micro amps.
Clean flame rod if necessary.
Replace module if necessary.