background image

Page 9/13

6W-5826

09-2012

IR motion detector comfort

T

150

90°  ...   45°

45°  ...   90°

fct

cfg

T

150

90°  ...   45°

45°  ...   90°

fct

cfg

T

150

90°  ...   45°

45°  ...   90°

fct

cfg

T

150

90°  ...   45°

45°  ...   90°

fct

cfg

T

150

90°  ...   45°

45°  ...   90°

fct

cfg

T

150

90°  ...   45°

45°  ...   90°

fct

cfg

~ 180°

~ 135°

~ 90°

Fig. 8: Setting the detection angle

Setting the detection performance

Test mode must be used to test the detection performance. In test mode, the motion detector 

works independent of brightness. Each detection switches the lighting and the status LED on for 

3 seconds. Thereafter motion detection will be deactivated for 2 seconds.
The motion detector is connected and ready for operation.

 

Setting the test mode. To do so, set the response brightness potentiometer (Fig. 5, 14) to 

the T position.

 

Leave the detection area and observe the switching behaviour. 

If the motion detector switches on without motion in the detection fi eld, then sources of in-

terference (see Installation location) are present or the sensitivity is set too high.

 

Reduce the sensitivity if necessary and blank out sources of interference by adjusting the 

detection angle or removing them.

 

Check the detection area using a detection test and adjust if necessary.

  If the detection area is too small, it can be extended via motion detector extension units.

Setting the response brightness

The response brightness is the brightness value saved in the motion detector; when this value 

is undershot the motion detector switches the connected load if movements are detected. The 

response brightness can be set between approx. 5 (

) over 

150 Lux

 (factory setting) to daytime 

operation (

). The 

 symbol stands for brightness-independent switching. The response bright-

ness can be variably adjusted in the intermediate areas.

  In order to control the lighting in stairwells in accordance with DIN EN12464-1, 2003-3, 

select the 

150 Lux

 potentiometer setting.

 

Turn the response brightness potentiometer (Fig. 5, 14) to the desired position.

  To save the current ambient brightness as response brightness, use the Teach-In function 

(see Setting the response brightness via Teach-In function).

  As the brightness evaluation only takes place via the main unit, there is no need to set the 

response brightness on extension units.

Set delay time

The delay time is the period of time saved in the motion detector which is the shortest time that 

the lighting is switched on for when the response brightness is undershot and motion is detec-

ted. 

Содержание 8534 12 series

Страница 1: ...comply with these installation instructions may result in damage to the device fire or other hazards Due to its detection behaviour the device is not suitable for use in burglary detection or alarm sy...

Страница 2: ...detected movement restarts the delay time The light will be switched off if no additional movements are detected in the detection area and the set delay time has elapsed On flush mounted dimmer The li...

Страница 3: ...ecuted by pushing the button 7 on the motion detector A short press of the button switches the operating modes The operating mode is displayed via the status LED behind the optics cover of the motion...

Страница 4: ...ched on via a mechanical push button extension unit For extension unit operation the lighting is switched on independently of the set brightness threshold When using the flush mounted dimmers the last...

Страница 5: ...ts the current ambient brightness and saves it as response brightness Setting of the response brightness via Teach In function and via the brightness potentiome ter has the same priority Teach In over...

Страница 6: ...30 s and changes to switching dimming ope ration Energy saving lamps are switched ON at a brightness level of at least 50 brightness in order to ensure an ignition process 4 x 230 V LED lamp universal...

Страница 7: ...ule via the in terface between application and power module 6 As soon as voltage is supplied to the application module the status LED indicates the com patibility to the insert used Status LED display...

Страница 8: ...e brightness potentiometer Setting the detection area 1 75 m 1 1 m 8 m 8 m 180 2 m 4 m 6 m 8 m 10 m 12 m Figure 6 detection area of the motion detector for mounting height 1 1 m 2 m 6 m 6 m 4 m 6 m 8...

Страница 9: ...n area using a detection test and adjust if necessary If the detection area is too small it can be extended via motion detector extension units Setting the response brightness The response brightness...

Страница 10: ...the sensitivity Detection is factory set to maximum sensitivity If there are frequent incorrect detections the sensitivity can be reduced Turn the sensitivity potentiometer Fig 5 9 to the desired posi...

Страница 11: ...ction for the motion detector is locked via the Motion and brightness dependent switching on switching off of the load Activate the presence simulation Activate permanent OFF Activate permanent ON 16...

Страница 12: ...to control other motion detectors Briefly press the button on the hand held transmitter The controlled motion detector does not accept any further setting commands Briefly press the button on the hand...

Страница 13: ...mal changes to the product in the interest of tech nical progress Our products are under guarantee within the scope of the statutory provisions If you have a warranty claim please contact the point of...

Отзывы: