USER HANDBOOK 1.0 | DC2115, ET2115
Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com
21-0099-82-00-00-003 | 270010900_Anwenderhandbuch_DC-ET2115_EN.docx
63
Dialog Controller
DC2115
Shock resistance
Vibration
sinusoidal (EN 60068-2-6) test: Fc 10…150 Hz, 10 m/s²
Shock
15 G (approx. 150 m/s²), 11 ms duration, sinusoidal half-wave (EN
60068-2-27)
Test: Ea
EMC, protection rating
Emitted interference
EN 61131-2; EN 61000-6-3, residential areas
Resistance to interference
EN 61131-2, industrial zone
Protection class
III
Insulation resistance
EN 61131-2; 500 V DC test voltage
Protection rating
IP20 (front IP65)
Power supply (24 V power)
Supply voltage
+24 V DC (–15 % / +20 %) SELV max. ripple component 5%
Power consumption
Max. 0.8 A, peak current 1.2 A at +24 V DC
Power consumption, dig. Out-
puts
Depending on the output load, max. 2 A continuous rating
Protection against reverse po-
larity
Yes
Ethernet interfaces
No. / type of interface
1x 10/100 Base T
Connection system
RJ45
EtherCAT interface
No. / type of interface
1x EtherCAT (EtherCAT master)
Connection system
RJ45
CAN bus interface
No. / type of interface
1x CAN bus
Protocols
CAN-Bus and/or CANopen master
Serial interfaces
No. / type of interface
1 x RS-232;
1 x RS-485
Protocols
Modbus RTU
USB interfaces
No. / type of interface
2 x host USB 2.0 / USB connector port A
Number of insertion/withdrawal
cycles
max. 1000