Operating manual
04_GB
ACP 3000 — 0.37–15.0
37
Berges electronic
•
D–51709 Marienheide-Rodt
•
Tel. 02264/17-0
•
Fax 02264/17126
NOTES:
1) VIN1/VIN2 changeover via PS3.
2) Data codes 6 up to 9 select the ACP EMOP control programs. With codes 6 or 7 (EMOP)
selected, commanded output frequency returns to
31-FMIN
when the drive is stopped.
With codes 8 or 9 (EMOP1) selected, commanded output frequency remains at the pre-
vious setpoint. See table above for proper usage.
◊
Value range: 0–11
Default: 3
EMOP/EMOP1 Control Terminal Logic Table
(Electronic Motor Potentiometer)
DATA
CODE
SPEED CONTROL
START/STOP CONTROL
0
Keypad
Keypad (FWD only)
1
VIN Terminals
1)
Keypad (FWD only)
2
Keypad
Terminals (2-Wire Maintained Contact)
3
VIN Terminals
1)
Terminals (2-Wire Maintained Contact)
4
Keypad
Terminals
(3-Wire Momentary, RUN/JOG via PS3)
5
VIN Terminals
Terminals
(3-Wire Momentary, RUN/JOG via PS3)
6
EMOP
2)
(Electronic motor potentiometer)
Terminals
(2-Wire, see section 7.7, page 61 and table below)
7
EMOP
2)
(Electronic motor potentiometer)
Terminals
(3-Wire, see section 7.7, page 61 and table below)
8
EMOP1
2)
(Electronic motor potentiometer)
Terminals
(2-Wire, see section 7.7, page 61 and table below)
9
EMOP1
2)
(Electronic motor potentiometer)
Terminals
(3-Wire, see section 7.7, page 61 and table below)
10
Keypad
Keypad (FWD and REV)
11
VIN Terminals
1)
Keypad (FWD and REV)
DESCRIPTION
FWD
REV
PS1
PS2
STOP
0
0
X
X
Speed = 0
1
1
X
X
FWD Decrease
1
0
1
X
FWD Hold
1
0
0
0
FWD Increase
1
0
0
1
REV Decrease
0
1
1
X
REV Hold
0
1
0
0
REV Increase
0
1
0
1
0 = inactive
1 = active
X = ignored