21.12.98
Operating manual
04_GB
ACP 3000 — 0.37–15.0
11
Berges electronic
•
D–51709 Marienheide-Rodt
•
Tel. 02264/17-0
•
Fax 02264/17126
3
Installation
3.1
Inspection
A. Upon receipt, unpack and carefully inspect for any damage sustained in transit (depres-
sion in the enclosure, damage to parts, missing parts).
B. Remove the cover (see page 25) and inspect the inverter for any apparent damage or
foreign objects. Ensure that all mounting hardware and terminal connection hardware is
properly seated, securely fastened, and undamaged.
C. Read the technical data label and ensure that the correct rated output and input voltage
for the application has been purchased.
D. If the inverter is to be stored for a long period of time, repack and store in a clean, dry
place, free from direct sunlight or corrosive fumes, and in a location where the ambient
temperature will not be less then -20 °C nor more than +60 °C.
3.2
General Rules for Installation
Improper installation of the inverter will greatly effect its life. Be sure to observe the following
points when selecting a mounting location. VIOLATING THE CONDITIONS LISTED BE-
LOW MAY VOID THE WARRANTY!
A. Mount the unit vertically and do not restrict the airflow to the heat sink fins on the back
of the controller. The fan and fins allow cooling of internal components. Any air restric-
tion could greatly reduce the life of the inverter, as well as resulting in nuisance overtem-
perature trips.
B. The ACP inverter generates heat, and therefore there must be a sufficient amount of
free space around the unit (see Figure 3.1). If the unit is accommodated in a housing
together with a different unit, the prescribed minimum distances must be observed so
that adequate ventilation can be ensured.
C. If the inverter has to be installed in a different position, external cooling is required for
full capacity utilization. In certain circumstances, the internal air circulation does not suf-
fice when installing the unit in a control cabinet with a small volume. Therefore, when
installing the unit, you must ensure that a heat buildup is prevented.
D. Do not mount the ACP near heat generating equipment, or in direct sunlight. BERGES
inverters are generally designed so that they can be operated at ambient temperatures
of 0 °C to +50 °C (IP 00) or 0 °C to 40 °C (IP 21) and at a relative humidity of up to 90%.
The occurrence of condensate must be avoided!