10.2.2 Alarms queue
10.2.3 Variables accessible solely via supervision
cH
/
Compressor run hours
-
0
999
10h
I
137
R
U
A1
Digital input 1 polarity:
0= Active with open contact
1= Active with closed contact
1
0
1
-
D
44
R/W
U
A2
Digital Input 1:
0= Relay inactive
1= External alarm
2= External blocking alarm
3= Pressure switch alarm
4= Remote ON/OFF
4
0
4
-
I
149
R/W
U
A3
Digital input 1 alarm delay (if
A2=3 minutes)
0
0
999
s
(min)
I
151
R/W
U
A4
!
Digital input 2 polarity:
0= Active with open contact
1= Active with closed contact
0
0
1
-
D
45
R/W
U
A5
Digital Input 2:
0= Relay inactive
1= External alarm
2= External blocking alarm
3= Pressure switch alarm
4= Remote ON/OFF
0
0
4
-
I
150
R/W
U
A6
"
Digital input 2 alarm delay (if A5=3
minutes)
0
0
999
s
(min)
I
152
R/W
U
A7
$
Number of pressure switch trips
1
1
15
-
I
154
R/W
U
A9
%
Temperature alarm delay
60
0
0
999
s
I
155
R/W
U
A10
Temperature alarm delay at
controller ON
60
0
999
min
I
156
R/W
U
rev
*'
Firmware update
-
0
99.9
-
A
0
R
U
Parameter Label
Description
Value
Min.
Max.
U.M.
Type ModBus R/W
Lev.
AL3
Alarm duration E03
0
999
min
I
145
R
U
AL4
!
Alarm duration E04
0
999
min
I
146
R
U
AL5
Alarm duration E05
0
999
min
I
147
R
U
AL6
"
Alarm duration E06
0
999
min
I
148
R
U
Description
Value
Min.
Max.
U.M.
Type ModBus R/W
Compressor status
-
0
1
-
D
0
R
EV1 status
-
0
1
-
D
1
R
Alarm status
-
0
1
-
D
2
R
Discharge status
-
0
1
-
D
3
R
EV2 status
-
0
1
-
D
4
R
DI1 status
-
0
1
-
D
5
R
DI2 status
-
0
1
-
D
6
R
Probe -BET faulty alarm (E01)
-
0
1
-
D
9
R
Probe -BEAOT faulty alarm (E02)
-
0
1
-
D
10
R
-BET high temperature alarm (E03)
-
0
1
-
D
14
R
-BEAOT high temperature alarm (E04)
-
0
1
-
D
15
R
-BET low temperature alarm (E05)
-
0
1
-
D
16
R
-BEAOT low temperature alarm (E06)
-
0
1
-
D
17
R
Parameter Label
Description
Value
Min.
Max.
U.M.
Type ModBus R/W
Lev.