9 . 2
A l a r m s t a b l e
Display
Alarm cause
Buzzer
Reset
Compressor
Alarm relay
Icon
E01
BET probe faulty alarm
On
automatic
OFF
See parameter “AA”
E02
Probe -BEAOT faulty alarm
On
automatic
See parameter “AA”
E03
-BET high temperature alarm
On
automatic
See parameter “AA”
E04
High temperature alarm
-BEAOT
On
automatic
See parameter “AA”
E05
Low temperature alarm -BET
On
automatic
OFF
See parameter “AA”
E06
Low temperature alarm
-BEAOT
On
automatic
OFF
See parameter “AA”
E07
Eeprom error: unit parameters
On
automatic
OFF
See parameter “AA”
E08
Eeprom error: operating
parameters
On
automatic
OFF
See parameter “AA”
E09
DI1 display only warning
On
automatic
See parameter “AA”
E10
DI1 delayed alarm
On
automatic
OFF
See parameter “AA”
E11
DI1 alarm after multiple trips
On
Manual
OFF
See parameter “AA”
E12
DI2 display only warning
On
automatic
See parameter “AA”
E13
DI2 delayed alarm
On
automatic
OFF
See parameter “AA”
E14
DI2 alarm after multiple trips
On
Manual
OFF
See parameter “AA”
E15
Compressor maintenance
warning
On
Manual
See parameter “AA”