C
HAPTER
5
INSTALLATION
ATTENTION
Before installing or operating these dryers, ensure that all personnel involved have read and understood Chapter 2
“Safety” in this manual.
ATTENTION
It is mandatory to install a prefilter upstream of the dryer to avoid exchanger fouling problems. It is good practice to
install also a coalescent deoiler filter.
5 . 1
L o c a t i o n
1. The unit can be installed either outdoors or in an enclosed environment, depending on the degree of IP protection
of the electrical panel and the unit itself.
2. If the unit is installed indoors the place of installation must be well ventilated. In certain cases it may be necessary
to install ventilation fans or extractor fans in order to reduce room temperature.
3. The ambient air must be clean, avoid sea ambients (brackish air), and not contain flammable gas or corrosive
solvents.
4. The minimum and maximum working ambient temperature are specified on the unit data plate. Ensure that the
unit is not installed in flows of hot air emitted by other equipment.
In extremetemperature conditions, the protection devices may trip.
5. Do not obstruct or interfere with the air flow produced by the unit; comply strictly with the minimum spaces/
distances specified in the installation drawings.
6. The machine must be installed on a perfectly horizontal flat surface, built and calculated to withstand the machine’s operating
weight, especially in the contact points highlighted in the installation drawing.
In the event of installations which fail to
comply with the above requirements, the manufacturer’s warranty cover will immediately become null and void
and the unit could malfunction or even lock out.
7. Leave free space around the unit for access during service interventions (see Attachments).
8. Do not install the plant in sites exposed to strong winds; if unavoidable, install suitable windscreens.
See point 1.