Parameter 

 

 

55 

  

 

64  

 

 

71

 

 

          Liquid gas 

          Liquid gas 

         Liquid gas 

 

 

G20  G30   G31  G20  G30   G31 

G20  G30 

G31

Lower Wobbe index 

 

 

 

 

 

 

 

 

 

 

(at 15 °C - 1013 mbar) 

MJ/m3  

45,7   80,9 

71,0   45,7   80,9 

71,0   45,7 

80,9 

71,0

Rated supply pressure 

mbar  

20 

28 

37 

20 

28 

37 

20 

28 

37

 

mm H2O  (203,9) (285,5)  (377,3) (203,9) (285,5)  (377,3)  (203,9) (285,5)  (377,3)

Minimum supply pressure 

mbar 

13,5 

 

 

13,5 

 

 

13,5

 

 mm H2O  (137,7) 

 

 

 

(137,7) 

 

 

 

(137,7)

Main burner - 2 nozzles  

Ø mm  

4,60   2,60**   2,60**   5,00   2,85**   2,85**   5,40   3,00**   3,00**

Maximum gas flow rate, CH (*) 

m3/h  

6,40  

 

 

 

7,40  

 

 

 

8,29

 

kg/h  

 

4,50 

4,50  

 

5,50   5,50  

 

6,20 

6,20

Maximum pressure downstream from  

 

 

 

 

 

 

 

 

 

 

valve in central heating mode 

mbar ∆p  

12,5   25,5   34,0   12,8   25,5   34,5   12,5   24,5   34,0

 

mm H2O ∆p  127  

260 

 346   130   260 

 351 

 127   250   346

2.4 

 

Technical specifications

(*) Temperature 15°C; Pressure 1013 mbar

Description

  

55 64 71

Rated heat input in central heating mode 

kW  61,0 70,5 79,0

 

kcal/h  52460  60630 67940

Rated heat output in central heating mode 

kW 

55,0 

63,5 

71,1

 

kcal/h  47300  54600 61150

Consumption 

W   23

Boiler class 

 

 

II 2H3+

Power supply 

V ~ Hz 

 

230 ~ 50

Index of protection 

IP 

 

40

Losses from stack and casing with burner off 

1,12 

1,26 

1,05

Central heating section

Maximum working pressure - Maximum temperature 

bar - °C 

 

3 - 100

CH water temperature adjustment range  

°C 

 

34-82

Gas pressure

Rated gas pressure (G20) 

mbar 

 

20

Rated gas pressure (G30 - G31) 

mbar 

 

28-30/37

Water connections

CH circuit flow - CH circuit return 

Ø 

 

1"1/4

Gas supply 

Ø 

1/2" 

3/4"

Emissions with G20 gas

 

CO s.a. below 

p.p.m. 

34 

31 

52

 CO2 

4,90  5,75 5,70

 

NOx (according to EN 297) 

 

 

class 1

 

Flue gas ∆t  

°C 

113 

123 

130

Boiler dimensions

Height  

mm 

 

850

Width  

mm 

 

450

Depth  

mm 

712 

795 

878

Weight  

kg 

190 

225 

251

Содержание NOVELLA 55-64-71 RAP

Страница 1: ...Installation Manual NOVELLA 55 64 71 RAP Boilers Cast Iron Base EN Installation Manual...

Страница 2: ...2 The following symbols are used in this manual b CAUTION Indicates actions that require caution and adequate preparation a STOP Identifies actions that you MUST NOT do...

Страница 3: ...diagram 12 3 INSTALLATION 13 3 1 Installation standards 13 3 2 Place of installation 13 3 3 Installation in existing system 13 3 4 Water connections 14 3 5 Electrical connections 14 3 6 Gas connectio...

Страница 4: ...ve at least the following operations performed switch the boiler OFF at the control panel and at the mains power switch close the boiler s fuel cock central heat ing circuit shut off cock and domestic...

Страница 5: ...ards and are enclosed in a functional control panel integrated in the body of the appliance NOVELLA boilers use total shut down logic and do not waste energy because they only start up when heat is a...

Страница 6: ...thermostat 5 Water circuit drain cock 6 Thermocouple 7 Burner 8 Gas supply solenoid valve 9 Name plate Key 10 Main switch 11 Central heating temperature control 12 Central heating temperature gauge 1...

Страница 7: ...ifications Temperature 15 C Pressure 1013 mbar Description 55 64 71 Rated heat input in central heating mode kW 61 0 70 5 79 0 kcal h 52460 60630 67940 Rated heat output in central heating mode kW 55...

Страница 8: ...installation and servicing may be ren dered difficult Fig 2 4 2 6 Material supplied The boiler is delivered in a wooden cage Proceed as follows to remove this remove the staples fixing the wooden cag...

Страница 9: ...6 unscrew the nut D from the top rear tie rod fig 2 7 fit the second lifting plate E over the end of the tie rod F Make sure that the sec ond lifting plate is diagonally opposite that fitted previousl...

Страница 10: ...8 Overall dimensions and water fittings Fig 2 9 2 9 Water circuit Key A Water circuit drain cock B CH circuit temperature control sensor C Safety thermostat sensor D CH circuit temperature gauge senso...

Страница 11: ...p of the right size bear in mind the boiler s water side pressure drop as shown in the following graph Fig 2 11 bOn initial start up and at least every year check that all the pumps in the system rota...

Страница 12: ...or automatic manual FU Fuse LV LED indicator mains power LR LED indicator flue gas temperature alarm TR Central heating temperature control TS Safety thermostat manual reset TF Flue gas thermostat man...

Страница 13: ...gas supplied The type of gas is specified on the packaging label and on the boiler s own name plate Make sure that the flue is able to withstand the temperature of the flue gases and that it has been...

Страница 14: ...5 Electrical connections Use a multi pole disconnector with a contact gap of at least 3 mm to connect the appliance to the mains electricity supply The appliance functions on an alternating current s...

Страница 15: ...necessary connection to the ter minal strip A Connect up the optional room thermostat and or timer as shown in the electrical wir ing diagrams in this manual Connect up the electrical power supply fig...

Страница 16: ...es are thor oughly clean Fit a suitably sized filter in the gas supply pipe if the gas supply contains any solid particles bThe gas supply line must be suitable for the flow rate demanded by the burne...

Страница 17: ...res condensate and mechanical stress bNOVELLA boilers are equipped with a flue gas thermostat located inside the hood This thermostat shuts down the boiler immediately in the event of flue gas blowbac...

Страница 18: ...he circuit until the pressure gauge reads out a value of 1 5 bar cold Close the water circuit shut off cocks fig 3 10 3 9 Emptying the water circuit Turn the electricity supply off by switching the bo...

Страница 19: ...l connections to the mains supply and to the system s control and safety devices have been made correctly check that the flue is properly constructed 4 2 Ignition Once you have completed all the prepa...

Страница 20: ...alve a number if times until the pilot burner lights fig 4 10 Hold down the ignition knob on the gas valve for about another 20 seconds after the pilot burner lights then release it Turn the ignition...

Страница 21: ...shown by the gas plate and have been calibrated in the factory using the values listed in the table tolerance 5 If the boiler needs new settings after repairs have been made the gas valve changed or...

Страница 22: ...disabled To do so proceed as follows Unscrew the screw D Screw the pressure regulator screw E all the way in Replace the plug D with the blind plug pro vided in the kit Unscrew the pressure measuremen...

Страница 23: ...ty the central heating system if there is any risk of freezing Contact your local Technical Assistance Centre if you encounter any problems in completing the above procedure IMPORTANT Also perform the...

Страница 24: ...ormally consists of the following operations remove encrustations from the burner remove encrustations from the heat exchangers check and clean the flue pipes check the efficiency of the external casi...

Страница 25: ...25 7 OPTIONAL ACCESSORIES Wall mounted weekly timer thermostat fig 7 1 RO120 storage cylinder fig 7 2 Back draught shutter 180 cod 480213 200 cod 480214 Fig 7 1 Fig 7 2 Fig 7 3...

Страница 26: ...26...

Страница 27: ......

Страница 28: ...proving its products and therefore reserves the right to modify the characteristics and specifications of the appliance described in this manual at any time and without prior notice The contents of th...

Отзывы: