9
ENGLISH
MENU
DEFAULT VALUE
MINIMUM
VALUE
MAXIMUM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
SETTINGS
USER
TIME & DATE
USER
LANGUAGE
ITALIANO / ENGLISH
USER
BACKLIGHT
5 min
1 min
15 min
USER
TIME SCHEDULE
USER
MAIN
USER
Only if POR = 1
ZONE1
USER
Only if POR = 1
ZONE2
USER
Only if POR = 1
DHW
USER
DHW HEAT PUMP
USER
TECHNICAL
INSTALLER
INSTALLATION
INSTALLER
ZONES MANAGER
INSTALLER
MODIFY ZONE
MAIN
MAIN / ZONE1 / ZONE2
INSTALLER
ACTUATION TYPE
ITRF05/AKM
ITRF05/AKM
BE16
INSTALLER
Only MAIN zone
REQUEST TYPE
THERMOSTAT
THERMOSTAT / TEMPERATURE PROBE /
REC10 MASTER / REC10 SLAVE
INSTALLER
BE16 ADDRESS
- -
1
6
INSTALLER
Only zones with ACTUATION = BE16
HYDRAULIC CONF
DIRECT ZONE
DIRECT ZONE
MIXING ZONE
INSTALLER
Only zones with ACTUATION = BE16
ZONE TYPE
HIGH TEMP.
HIGH TEMP.
LOW TEMP.
INSTALLER
MIN CH SET
40°C (AT)
20°C (BT)
20°C
MAX CH SET
INSTALLER
MAX CH SET
80,5°C (AT)
45°C (BT)
MIN CH SET
80,5°C (AT)
45°C (BT)
INSTALLER
CHANGE NAME
INSTALLER
PI - PROPORTIONAL
5
0
99
SERVICE
Only mixing zones with ACTUATION=BE16
PI - INTEGRAL
10
0
99
SERVICE
Only mixing zones with ACTUATION=BE16
VALVE RUN
120 sec
0 sec
240 sec
SERVICE
Only mixing zones with ACTUATION=BE16
CLOSING AT POWER ON
140 sec
0 sec
240 sec
SERVICE
Only mixing zones with ACTUATION=BE16
OUTLET OVER
55°C
0°C
100°C
SERVICE
Only BT zones with ACTUATION =BE16
OUTLET OVER TEST TIME
0min
0min
240min
SERVICE
Only BT zones with ACTUATION =BE16
OUTLET OVER WAIT TIME
2min
VALVE RUN
240min
SERVICE
Only BT zones with ACTUATION =BE16
OUTLET OVER REST TIME
2min
0min
240min
SERVICE
Only BT zones with ACTUATION =BE16
FREEZE PROT TEMP
6°C
-20°C
50°C
SERVICE
Only zones with ACTUATION = BE16
FREEZE PROT OFFSET ZONE
5°C
1°C
20°C
SERVICE
Only zones with ACTUATION = BE16
FREEZE PROT T EXT
10°C
0°C
100°C
SERVICE
Only zones with ACTUATION = BE16
POR
0 (1 if REC10
in the AMBIENT)
0
1
INSTALLER
ADD ZONE
INSTALLER
DELETE ZONE
INSTALLER
SENSOR CALIBRATION
0,0°C
- 6,0°C
6,0°C
INSTALLER
SYSTEM RESET
INSTALLER
FACTORY SET