TIVANO WALL - Allarmi / Troubleshooting

EFFECT

CAUSE

SOLUTION

The ventilation is delayed with 

 

respect to the new temperature or 

function settings.

The circuit valve requires a certain 

time to open and therefore to make 

the hot or cold water circulate inside 

the device.

Wait 2 or 3 minutes to allow the 

 

circuit valve to open.

The device does not activate the 

 

ventilation.

Cold or hot water is missing from the 

system. 

Make sure the boiler or the water 

 

cooler are on.

The ventilation does not start even if 

the water circuit is filled with hot or 

cold water.

The hydraulic valve stays closed

Demount the body of the valve and 

check if the water circulation is 

 

restored.
Check the valve operation feeding 

it separately to 230 V. If you were 

to turn, the problem may be in the  

electronic control.

The ventilation motor is jammed or 

burnt.

Check the motor windings and check 

if the fan rotates freely.

The wirings are not correct,

Check all wirings.

The device is losing water in heating 

mode.

Leaks at the hydraulic connections of 

the system.

Check the leak and tighten the 

 

connections.

Leaks at the valves unit.

Check the condition of the gaskets.

There is dew on the front panel.

Detaches thermal insulation.

Check the correct positioning of 

the thermal and acoustic insula-

tions paying particular attention to 

the front one located on top of the  

finned coil.

There are water drops on the air vent.

High humidity conditions (>60%) 

 

might generate condensation, espe-

cially at minimum ventilation speeds.

As soon as the level of relative 

 

humidity drops, the phenomena 

 

disappears. However, a few water drops  

falling inside the device will not 

 

cause any malfunction.

The device is losing water in cooling 

mode.

The condensate tray is clogged.

Slowly pour a bottle of water in the 

lower section of the battery to check 

the drainage; if necessary clean the 

tray and/or improve the slope of the 

drain pipe.

The condensate discharge pipe does 

not have the slope required for 

 

correct drainage.

The connection pipes and the valves 

unit are not well insulated,

Check the pipes insulation.

The device generates excessive noise.

The fan touches the structure.

Check if the filters are dirty and clean 

them if necessary

The fan is unbalanced.

The unbalancing generates excessive 

machine vibrations: replace the fan.

Check if the filters are dirty and clean 

them if necessary

Clean the filters

Содержание 20148838

Страница 1: ...TIVANO WALL Manuale Installatore Installation and Operation Manual EN IT Manuale Installatore Installation and Operation Manual...

Страница 2: ...rective 2014 35 UE RoHS Directive 2011 65 UE WEEE Directive 2012 19 UE Gamma Range Modello Codice TIVANO WALL 27 20148838 TIVANO WALL 41 20148839 TIVANO WALL 57 20148840 Model Code TIVANO WALL 27 2014...

Страница 3: ...IVANO WALL 27 41 57 23 3 4 Descrizione del funzionamento con telecomando o display touch screen TIVANO WALL 27 41 57 24 3 5 Utilizzo dell apparecchio 27 4 MANUTENZIONE 4 1 Manutenzione 28 4 2 Pulizia...

Страница 4: ...degli infortuni Rispettare le leggi in vigore nel Paese in cui viene installata la macchina relativamente all uso e allo smaltimento dell imballo dei prodotti impiegati per pulizia e manutenzione e p...

Страница 5: ...without the authorisation and directions of the manufacturer Do not stand sit and or place objects on the unit Do not pull detach or twist the electrical wires coming out of the unit even when the uni...

Страница 6: ...difficoltosa qualsiasi operazione di installazione e manutenzione The technical tag shows all technical and performance data of the unit Should the tag get lost please ask for a duplicate tag from th...

Страница 7: ...h 320 430 540 Portata d aria med Air flow rate med m3 h 250 340 410 Portata d aria min Air flow rate min m3 h 140 230 310 Tensione di alimentazione Supply voltage V ph Hz 230 1 50 230 1 50 230 1 50 Po...

Страница 8: ...carico 1 8 Charts of Water flow Pressure drop Perdita di carico kPa Pressure drop kPa Portata d acqua kg h Water ow kg h 27 41 57 Perdita di carico kPa Pressure drop kPa Port W 0 5 1 2 4 8 16 30 150 7...

Страница 9: ...so il ventil convettore viene posto in stand by AIR Sonda aria DISPLAY cablaggio display pannello H2 water temperature probe 10 k M1 fan motor DC inverter Y1 water solenoid valve 230V 50Hz 1A powered...

Страница 10: ...come into contact with water in environments with oil mists in environments subject to high frequencies Make sure that the wall on which you intend to install the unit has an appropriate structure an...

Страница 11: ...ing bracket B Coil water inlet C Coil water outlet D Condensate drain E Connector terminal F Cable clamp 20 mm 20 mm 120 mm min 2000 mm pavimento floor 2 5 Distanze minime di installazione Nella figur...

Страница 12: ...ta esagonale presenti ai lati del pannello frontale per poter rimuovere il pannello frontale estetico A FIANCHETTI B PANNELLO FRONTALE ESTETICO 2 6 Opening of aesthetic parts for installation For desc...

Страница 13: ...alto rimuovendo prima le due viti che fissano al fianco sinistro la struttura del display se presente A FILTRI B FIANCHI LATERALI 3 Wheels and rise the filters 4 Remove the fixing screws of side pane...

Страница 14: ...alla dima di installazione in dotazione riportata successivamente A CASSETTA DA INCASSO B TUBAZIONI IDRONICHE DI RACCORDO C TUBO DRENAGGIO CONDENSA D TIVANO WALL 2 7 Wall mount For smooth installatio...

Страница 15: ...fe e la sua stabilit 6 Fare attenzione all inclinazione del ventilconvettore rispettando la corretta inclinazione come in figura a fondo pagina 1 3 2 4 G 1 NO A TASSELLI B STAFFE 1 Use the paper templ...

Страница 16: ...16 TIVANO WALL Installazione Intallation 2 8 Dima di installazione quotata 2 8 Installation template measured...

Страница 17: ...17 TIVANO WALL Installazione Installation...

Страница 18: ...alla laterale sotto gli attacchi idraulici Se possibile fare defluire il liquido di condensa direttamente in una grondaia o in uno scarico di acque bianche In caso di scarico nella rete fognaria si co...

Страница 19: ...Connect the drain connection of the drain pan that collects the condensate fluid to a hose and tighten it properly Make sure the drip guard extension is present and that it has been properly installe...

Страница 20: ...riferiti ad una lunghezza massima delle linee pari a 15 m I cavi devono essere di tipo adeguato al tipo di posa in accordo con le norme CEI in vigore 27 41 57 SEZIONE CONDUTTORE DI ALIMENTAZIONE FASE...

Страница 21: ...cciavite sullo sfiato dell attacco batteria posto pi in alto vedi figura sotto Quando comincia ad uscire acqua dalle valvole di sfiato dell apparecchio chiuderle e continuare il caricamento fino al va...

Страница 22: ...ere fatto funzionare utilizzando i tasti del display touch screen a bordo macchina It is possible to select the various modes by pressing the buttons see Description of machine functioning para graph...

Страница 23: ...ione del flusso d aria Tasto controllo della velocit del ventilatore Tasto impostazione funzione Timer 1 Tasto impostazione funzione Timer 2 Sensore di luminosit Termometro digitale 1 7 barrette rosse...

Страница 24: ...serve per l attivazione e la disatti vazione dell apparecchio per brevi periodi In caso di prolungato arresto dell apparecchio questo deve essere disattivato staccando l interruttore generale o toglie...

Страница 25: ...le non deve mai essere forza to manualmente In raffrescamento la posizione del deflettore viene resettata ogni 30 min per evitare formazione di rugiada Controllo della velocit del ventilatore Premendo...

Страница 26: ...this mode ventilation is set on minimum speed This mode should be activated right before going to sleep In cooling mode the set temperature is risen by 1 C after one hour and by another degree after...

Страница 27: ...azione servirsi sempre del comando apposito Nel caso vi fossero perdite d acqua dall apparecchio necessario spegnerlo immediatamente e togliere l alimentazione elettrica Chiamare quindi il Servizio Te...

Страница 28: ...leaning Disconnect the unit from the power supply before each cleaning and maintenance intervention by setting the main power supply switch to off Wait for the components to cool down in order to avoi...

Страница 29: ...he frequency is semiannual in domestic environment Pulizia setti filtranti aspirare la polvere dai filtri con un aspirapolvere lavare sotto acqua corrente senza utilizzare detergenti o solventi i filt...

Страница 30: ...y Non possibile attivare nessun funziona mento dell apparecchio CP Contatto presenza CP aperto L apparecchio si attiva solo se il contatto chiuso Verificare la connessione dei mor setti LAMPEGGIANTE T...

Страница 31: ...e il corpo valvola e verificare se si ripristina la circolazione dell ac qua Controllare lo stato di funziona mento della valvola alimentandola separatamente a 230 V Se si dovesse attivare il problema...

Страница 32: ...Leaks at the valves unit Check the condition of the gaskets There is dew on the front panel Detaches thermal insulation Check the correct positioning of the thermal and acoustic insula tions paying p...

Страница 33: ...33 TIVANO WALL Allarmi Troubleshooting...

Страница 34: ...34 TIVANO WALL Allarmi Troubleshooting...

Страница 35: ...35 TIVANO WALL Allarmi Troubleshooting...

Страница 36: ...onamentodituttalasuaproduzione lecaratteristicheestetiche edimensionali idatitecnici gliequipaggiamentiegliaccessori possonoesseresoggettiavariazione The manufacturer strives to continuously improve a...

Отзывы: