INSTRUCTIONS PUMP TYPE SUNTEC A2L 65C - 75C
Suction line tables
The suction line tables consist of theo-
retically calculated values where the
pipe dimensions and oil velocity have
been matched so that tur-bulences will
not occur. Such tur-bulences will result
in increased pressure losses and in
acoustic noise in the pipe system. In
addition to drawn copper piping a pipe
system usually comprises 4 elbows, a
non-return valve, a cut-off valve and
an external oil filter.
The sum of these individual resi-
stances is so insignificant that they
can be disregarded. The tables do not
include any lengths exceeding 100
m as experience shows that longer
lengths are not needed.
The tables apply to a standard fuel
oil of normal commercial quality
accor-ding to current standards. On
commis- sioning with an empty tube
system the oil pump should not be
run without oil for more than 5 min.
(a condition is that the pump is being
lubricated during operation).
The tables state the total suction line
length in metres at a nozzle capacity
of 9,5 Gph. Max. permissible pres-
sure at the suction and pressure side
is 2,0 bar.
Components
1. Nozzle outlet G 1/8" Stage 2
2. Pressure gauge port G 1/8"
3. Nozzle outlet G 1/8" Stage 1
4. Pressure gauge port G 1/8"
5. Vacuum gauge port G 1/8"
6. Return line G 1/4"
and internal by-pass plug
7. Suction line G 1/4"
8. Return plug
9. Pressure adjustment
10. Solenoid valve 1
11. Solenoid valve 2
Technical data
One or two-pipe system.
Viscosity range:
2-12 mm
2
/S
Pressure range:
8-15 bar
Rated voltage of coil:
220/240V
50/60 Hz
Oil temperature:
max 60°C
1-pipe system
Height
Pipe diameter
H
ø6 mm
m
m
With an underlying tank a 1-pipe-
system is not recommended
Two-pipe system
Height
Pipe diameter
H ø8mm ø10mm ø12mm ø14mm
m m m m m
0,0 20
54
116
150
-0,5 17
48 103 150
-1,0 15
41
89
150
-2,0 9
28 61 116
-3,0 4
14 33
65
-4,0 0
0
6
14
1-pipe system
Height
Pipe diameter
H
ø6 mm ø8 mm ø10 mm
m m m m
4,0
45
144
150
3,0
39
127
150
2,0
34
109
150
1,0
28
92
150
0,5
26
83
150
0,0
23
74
150
Two-pipe system
Height
Pipe diameter
H ø8mm ø10mm ø12mm ø14mm
m m m
m m
4,0 42
108
150 150
3,0 36
94
150 150
2,0 31
81
150 150
1,0 26
68
144 150
0,5 23
61
130 150
0,0 20
54
116 150
H
H