8
Bentone
2.6
Setting of ignition electrodes and brake
plate
a
b
c
Measurements according to EN 15036-1:2006
Alt.1 The noise level of the burner can be reduced by equipping the burner with
silencer. Installation must be done so it does not prevent air supply to the
burner.
Alt.2 The burner’s noise level can be reduced by connecting the burner’s air
intake to the air duct that opens into an appropriate location. Installation
must be done so it does not prevent air supply to the burner.
!
*NB It is important that the spark
does not strike against the brake
plate or nozzle.
a
b
c
2.5-3.5
7,0-9,0
1.0-2.0
Nozzle:
45° Solid/semisolid
60° Solid/semisolid
80° Solid/semisolid
Pump pressure:
10 bar (8-25 bar) depending on pump model
2.7
Nozzle and pump pressure
Due to different furnace geometries and capacities, it is not possible to
recommend a nozzle model.
2.5
Technical specification
B 40 A
Main supply
1)
230V, 1~, 3.0/3.1A, 50Hz, IP20
Max fuse rating
8A
El
min
preheater excluded
1.67A, 375W
El
max
preheater excluded
1.70A, 382W
P
SB
0
NO
X
-class
2
Noise level
83dBA
1)
Max operating current, see data plate.