List of Faults
Table 11 shows the meaning of fault messages and the
actions to take when they occur.
66
Expandable Hybrid Control Panel
ABSOLUTA
MESSAGE
DESCRIPTION
Zone
—-
(1)
The detector connected to the Zone with the label
Zone
001
2
is faulty
(masked, etc.). Call the Installer.
PS1
low Vout
(1)
The output voltage of Power station No. 1 (2, 3 or 4) is less than
10.6 V
. Call the Installer.
PS1
Vout1 LOW
(1)
The
O1
(
O2
or
O3
) output voltage of Power station No. 1 (2, 3 or 4) is less than
10.6 V
. Call the Installer.
PIN to default
The user PINs are NOT safe because they are the default factory ones. Change
the default PIN.
Inst. access
The installer has changed the programming of the control panel.
Panel bat. low
The Battery voltage of the Control panel is less than
11.4 V
.
Panel bat. fail
The control panel battery does not pass the Dynamic test. Call the Installer.
Panel NO batt.
The control panel battery is disconnected or absent. Call the Installer.
Panel bat.charg
The control panel is not capable to recharge the battery. Call the Installer.
Panel NO 220v
The Mains power of the Control panel has failed . Call the Installer.
Panel PSU
Switching power supply does not work. Call the Installer.
Panel low Vout
The output voltage of control panel is low. Call the Installer.
PS1 bat. low
The battery voltage of the Power station No. 1 (2, 3 or 4) is less than
10.9 V
. Call
the Installer.
PS1 bat. fail
The battery of Power station No. 1 (2, 3 or 4) does not pass the Dynamic test or it is
disconnected or the Fuse -protects against Battery polarity inversion- is broken.
Call the Installer.
PS1 NO batt.
Switching power supply of the Power station No. 1 (2, 3 or 4) does not work. Call
the Installer.
PS1 bat.charg
The Output voltage of the Switching power supply of the Power station No. 1 (2, 3
or 4), is outside the normal range min
10.2 V
max
14.7 V
. Call the Installer.
PS1 NO 220v
The Mains power of the Power station No. 1 (2, 3 or 4) has failed. Call the Installer.
PS1 PSU
Switching power supply of the Power station No. 1 (2, 3 or 4) does not work. Call
the Installer.
PS1 low Vout
The Power station No. 1 (2, 3 or 4) is not capable to supply the right output voltage.
Call the Installer.
PS1 bat. disc.
The battery of the Power station No. 1 (2, 3 or 4) is disconnected when you switch
on the Power station No. 1 (2, 3 or 4). Call the Installer.
PS1 SWT disc.
Switching power supply of the Power station No. 1 (2, 3 or 4) is disconnected. Call
the Installer.
PS1 Vout1 short
Short circuit on Output
O1
(
O2
or
O3
) of the Power station No. 1 (2, 3 or 4). Call the
Installer.
summer time
The Control panel Clock has been set/unset to Daylight savings time.
Fuse B
Fuse B is opened -protects the Siren Output.
Fuse zones
Zone Fuse is opened-protects the Zones power line.
Fuse BPI
BPI Fuse is opened-protects the BPI line.
Fuse Keybus
Keybus Fuse is opened-protects the Key-bus.
Inst. Maintenan.
The date of the periodic checks of the Installer has expired.
Surve.Maintenan.
The date of the periodic checks of the Central Station has expired.
Default Date
The Mains power of the Control panel has failed, and the internal clock went to the
default -hour/date-. Reprogramming Hour/Date.
Inst. access
The control panel programming has been changed.
Delinquency
The zone"Inactivity Time" has expired, from when the status zone is changed.
Tel. Line
Telephone line failure.
Tel. comm. FTC
A telephone message failed to reach destination.
WLS batt. low
Low Battery on one or more Wireless devices.
GSM Network
The GSM network cannot be found: wait for it to be reset. The SIM cannot be
found: contact your installer.
GPRS Network
The GPRS network cannot be found: wait for it to be reset.
Table 11
List of Faults:
1)
ONLY Grade 3 Control Panels;
2)
Depends on the zone fault label.