BENNING IT 115
Appendix A – Fuse table
- 63 -
Line safety switch, tripping characteristic K
Range of instantaneous tripping: 8 - 14 x I
N
Nominal
current
(A)
Disconnection time [s
]
35m
0.1
0.2
0.4
Minimum prospective short-circuit current (A)
0.5
7.5
7.5
7.5
7.5
1
15
15
15
15
1.6
24
24
24
24
2
30
30
30
30
4
60
60
60
60
6
90
90
90
90
10
150
150
150
150
13
195
195
195
195
15
225
225
225
225
16
240
240
240
240
20
300
300
300
300
25
375
375
375
375
32
480
480
480
480
Line safety switch, tripping characteristic D
Range of instantaneous tripping: 10 - 20 x I
N
Nominal
current
(A)
Disconnection time [s
]
35m
0.1
0.2
0.4
5
Minimum prospective short-circuit current (A)
0.5
10
10
10
10
2.7
1
20
20
20
20
5.4
1.6
32
32
32
32
8.6
2
40
40
40
40
10.8
4
80
80
80
80
21.6
6
120
120
120
120
32.4
10
200
200
200
200
54
13
260
260
260
260
70.2
15
300
300
300
300
81
16
320
320
320
320
86.4
20
400
400
400
400
108
25
500
500
500
500
135
32
640
640
640
640
172.8