BENNING IT 115
Appendix A – Fuse table
- 62 -
Line safety switch, tripping characteristic B
Range of instantaneous tripping: 3 - 5 x I
N
Nominal
current
(A)
Disconnection time [s
]
35m
0.1
0.2
0.4
5
Minimum prospective short-circuit current (A)
6
30
30
30
30
30
10
50
50
50
50
50
13
65
65
65
65
65
15
75
75
75
75
75
16
80
80
80
80
80
20
100
100
100
100
100
25
125
125
125
125
125
32
160
160
160
160
160
40
200
200
200
200
200
50
250
250
250
250
250
63
315
315
315
315
315
Line safety switch, tripping characteristic C
Range of instantaneous tripping: 5 - 10 x I
N
Nominal
current
(A)
Disconnection time [s
]
35m
0.1
0.2
0.4
5
Minimum prospective short-circuit current (A)
0.5
5
5
5
5
2.7
1
10
10
10
10
5.4
1.6
16
16
16
16
8.6
2
20
20
20
20
10.8
4
40
40
40
40
21.6
6
60
60
60
60
32.4
10
100
100
100
100
54
13
130
130
130
130
70.2
15
150
150
150
150
83
16
160
160
160
160
86.4
20
200
200
200
200
108
25
250
250
250
250
135
32
320
320
320
320
172.8
40
400
400
400
400
216
50
500
500
500
500
270
63
630
630
630
630
340.2