12
13
MENU
FUNCTION
DEFAULT
MEMO
LOGICS
TCA
The automatic closure is enabled or disabled.
Off: disabled automatic closure.
On: enabled automatic closure
(ON)
IBL
The multi-flat function is enabled or disabled.
On: enabled multi-flat function. The P.P. (Step-by-step) impulse or the impulse
of the transmitter has no effect in the opening phase.
Off: disabled multi-flat function.
(OFF)
IBCA
The PP and PED controls during the TCA are enabled or disabled.
On: PP and PED controls are disabled.
Off: PP and PED controls are enabled.
(OFF)
SCL
The rapid closure is enabled or disabled.
On: enabled rapid closure. With open gate or gate in the opening phase, the
activation of the photocell causes the automatic closure of the gate 3 sec after
its activation.
This function is enabled only with TCA:ON
Off: rapid closure disabled.
(OFF)
PP
The operating mode of the “P.P.” (Step-by Step) button and of the transmitter
is selected.
On: Operation : OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >
(OFF)
PRE
Forewarning flashing light enabled or disabled.
On: enabled forewarning flashing light. The flashing light is activated 3 sec be-
fore the motor starts.
Off: disabled forewarning flashing light.
(OFF)
HTR
The Service Man function is enabled or disabled.
On: Service Man operation.
The OPEN/CLOSE push buttons should be kept pressed for the entire operating
time.
Off: Automatic operation.
(OFF)
SLD
Raking is enabled or disabled.
On: Braking enabled.
Off: Braking disabled.
(OFF)
LTCA
The forewarning flashing light is enabled or disabled during the TCA time.
On: Flashing light enabled.
Off: Flashing light disabled.
(OFF)
CLOC
The OPEN input mode is selected.
On: OPEN input, with CLOCK function.
To be used for connection to timer for timed opening/closing. (CLOSED contact:
open gate. OPEN contact: normal operation).
Off: OPEN input, with OPEN function
(OFF)
ENC
The Encoder is enabled or disabled.
On: Encoder enabled.
Off: Encoder disabled.
(ON)
CVAR
The programmable code transmitters are enables or disabled.
On: Radio receiver enabled only for rolling-code transmitters.
Off: Receiver enabled for rolling-code transmitters and programmable code
transmitters (self-learning and DIPswitch) .
(OFF)
TREL
Check of OPEN and CLOSE relays is enabled or.
On: Check activated: if one of the 2 relays is faulty, the motor does not start and
the error message “ERR2” is displayed.
Off: no check to relays is carried out.
(OFF)
SOFT
Reduced speed starting is enabled or disabled.
On: Starting is performed at reduced speed for 2 seconds and then movement
is restored to normal speed.
Off: Reduced speed start is disabled.
(OFF)
OPCL
PP input as OPEN and PED input as CLOSED are enabled or disabled.
On: PP input is enabled as OPEN and PED input is enabled as CLOSED.
Off: PP and PED inputs are enabled with their function.
(OFF)