15
PARAmETERs, LoGiCs ANd sPECiAL FUNCTioNs
In the tables hereunder the single functions available in the control unit are shown.
mENU
FUNCTioN
miN-mAX-(default)
mEmo
PARA
m
ETER
s
TCA
Automatic closure time. It is activated only with “
TCA
”=ON logic.
At the end of the preset time, the control unit controls a closure opera-
tion.
1-240-(40s)
TM
Operating time. The operating time is adjusted during motor opening and
closing phases.
1-250-(90s)
Tped
The area covered by the gate during its partial opening movement (pe-
destrian) is adjusted.
20-250-(50 cm)
Tsm
The area covered by the gate during the braking phase is adjusted.
0 = braking disabled
0-250-(0 cm)
PMo
The torque applied to the motor in the opening phase is adjusted.*
1-99-(50%)
PMC
The torque applied to the motor in the closing phase is adjusted *.
1-99-(50%)
Pso
The torque applied to the motor during braking in the closing phase is
adjusted.*
1-99-(50%)
Psc
The torque applied to the motor during braking in the opening phase is
adjusted *
1-99-(50%)
SeaU
The intervention threshold of the anti-crashing device (Encoder) during
the phase at normal speed is adjusted.*
1:maximum sensitivity - 99: minimum sensitivity
0-99-(0%)
SEAR
The intervention threshold of the anti-crashing device (Encoder) during
braking is adjusted *.
1:maximum sensitivity - 99: minimum sensitivity
0-99-(0%)
TLS
Activated only with
SERL
:ON Logic. The activation time of the service light
is adjusted.
1-240-(60s)
Ibra
The force of the motor brake is adjusted.
0: disabled braking - 1:minimum braking - 99: maximum braking
0-99-(50%)
* WARNiNG: An incorrect setting of these parameters may cause danger.
Please comply with regulations in force!
mENU
FUNCTioN
dEFAULT
mEmo
L
o
G
iC
s
TCA
The automatic closure is enabled or disabled
On: enabled automatic closure
Off: disabled automatic closure
(ON)
IbL
The multi-flat function is enabled or disabled.
On: enabled multi-flat function. The P.P. (Step-by-step) impulse or the impulse
of the transmitter have no effect in the opening phase.
Off: disabled multi-flat function.
(OFF)
SCL
The rapid closure is enabled or disabled
On: rapid closure is enabled. When the gate is open or moving, the photocell
activation causes the automatic closure of the gate after 3 s. It is activated only
with TCA:ON
Off: rapid closure is disabled.
(OFF)
PP
The operating mode of “P.P. Push button” and of the transmitter are selected.
On: Operation : OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >
(OFF)
PRE
Forewarning flashing light enabled or disabled.
On: enabled forewarning flashing light. The flashing light is activated 3 s before
the starting of the motor.
Off: disabled forewarning flashing light.
(OFF)
LTCA
During the TCA time, the blinker is enabled or disabled.
On: Activated blinker.
Off: De-activated blinker.
(OFF)