- 18 -
Boiler location in regards to required handling space:
•
AA5 / AB5 basic setting rating according to
ČSN 33 2000-1 ed.2:2009
•
minimum of 600 mm handling space must be left in front of the boiler (applies for K14 boiler) and 1000
mm (applies for K20 and K25 boilers)
•
minimum distance between the back of the boiler and the wall must be 400 mm
•
minimum 500 mm clearance on the side of the boiler body (applies for K20 and K25 boilers) to enable
cleaning of the exchanger convection surface
•
minimum 500 mm clearance on the side of the fuel store to enable easy replenishment
•
minimum 350 mm clearance above the fuel store to enable easy replenishment
Fuel store installation and positioning:
•
To install the fuel store to the K14, K20 and K25 boilers follow separate appendix to BENEKOV boiler
operating and installation instructions.
•
The fuel store must be, in regards to the boiler body, positioned in such way as to ensure
reliable fuel
overflow
without the risk of clogging the flexible hose. The flexible hose can be shortened accordingly.
•
The angle o
f inclination between the feeder and the horizontal floor must be between 0 and 60 °, the
optimal inclinatoin
is 45 °.
Fuel location:
•
It is recommended to store the pellets in a dry place in their original
manufacturer’s packaging (PET bags
or „big bags“).
•
The pellets must not be stored behind the boiler or next to the boiler at a distance of less than 400 mm.
•
The manufacturer recommends keeping the distance between the boiler and the fuel to a minimum of
1 000 mm or place the fuel in a room separate to where the boiler is located.
Fig 8 Position of the K20 or K25 boiler in a boiler room
Содержание K14
Страница 1: ...BOILER OPERATION AND INSTALLATION GUIDE BENEKOV K14 BENEKOV K20 BENEKOV K25 ...
Страница 9: ... 9 Fig 3 BENEKOV K14 boiler basic dimensions ...
Страница 10: ... 10 Fig 4 BENEKOV K20 and K25 boiler dimensions ...
Страница 17: ... 17 Fig 7 Position of the K14 boiler in a boiler room ...
Страница 33: ... 33 Fig 17 Diagram of electrical connection of XS20 burner of the K14 boiler ...
Страница 34: ... 34 Fig 18 Diagram of electrical connection of XS26 burner of the K20 and K25 boilers ...