Device communication
34
iso1685FR(M)_D00002_02_M_XXEN/06.2017
6.1.6 Alarm and operating messages via the BMS bus
Messages are transmitted to a maximum of 12 BMS channels. All alarm and operating messages that may occur
are described below.
6.1.6.1 Alarm messages
6.1.6.2 Operating messages
Alarm
Channel
Meaning
Insulation fault alarm Ze/kΩ
1
Insulation impedance < response value
Z
an
(Active measuring method)
Alarm coupling
4
Terminal L1 and/or terminal L2 is not connected
Alarm E/KE
5
E-KE connection is not available
Device error alarm
7
Internal device error
U
N-PE
alarm
(Star point/earth)
8
Voltage U
N-PE
> response value U
an
(Passive measuring method)
Overtemperature coupling
terminal L1
10
Temperature of the coupling L1 > 150 °C
Overtemperature coupling
terminal L2
11
Temperature of the coupling L2 > 150 °C
Alarm
Channel
Meaning
Insulation impedance
Z
e
/kΩ
1
Insulation impedance ≥ response value
Z
an
System leakage capacitance
C
e
/n
F
2
Leakage capacitance
C
e
in nF
Insulation resistance
R
e
/kΩ
3
Insulation resistance R
e
in kΩ
Proposal
C
eto-set
6
Proposal for the system capacitance
Voltage U
N-PE
(Star point/earth)
8
Voltage
U
N-PE
Temperature coupling L1
10
Temperature of the coupling L1 > 150 °C
Temperature coupling L2
11
Temperature of the coupling L2 > 150 °C
Method of shutdown
12
Method by which the shutdown has occurred
• Active method
• Passive method
• Interference detection
Содержание ISOMETER iso1685FR
Страница 6: ...6 ...
Страница 10: ...Important information 10 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Страница 14: ...Safety instructions 14 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Страница 42: ...Diagram for the calculation of Ze 42 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Страница 44: ...Information about the measuring method 44 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Страница 50: ...INDEX 50 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Страница 51: ...INDEX 51 iso1685FR M _D00002_02_M_XXEN 06 2017 ...