![Bender ISOMETER iso1685FR Скачать руководство пользователя страница 30](http://html.mh-extra.com/html/bender/isometer-iso1685fr/isometer-iso1685fr_manual_2731645030.webp)
Installation, connection and commissioning
30
iso1685FR(M)_D00002_02_M_XXEN/06.2017
5.3.2 Commissioning of the ISOMETER® iso1685FRM
System = IT system ?
Device connection
U
n
< 400 V ?
U
N-PE
< 3 kV,
U
L1‘-PE
< 3kV ?
iso1685FRM is not suitable
No
Deenergize the installation before
connecting the device.
E and KE to PE
System to L1/+, L2/-
Optional device connection
BMS bus to A, B, S
Supply voltage to A1/A2
Signal peripherals at K1, K2, K3
11-12-14, 21-22-24, 31-32-34
Connect the iso685FRM to the
Analogue Modbus Converter
M7024:
i.e. A to (Y)DATA+, B to (G)DATA-
Connect “Iout0“ of the Analogue
Modbus Converter M7024 to the
“24 V“ of DC power supply 1
Connect the external analogue
input to “AGND“ of the Analogue
Modbus Converter M7024 and to
“GND“ of DC power supply 1
Switch on supply voltage
Switch on mains voltage
No
Yes
Yes
Yes
iso1685FRM is not suitable
Connection fault or device error:
check the connections
Should factory settings
be kept?
No
Yes
Make the settings via the
BMS bus
Are the alarm LEDs
lighting?
No
Yes
The set response value is too low
- adjustment required
Function test with a suitable
ohmic resistance between the
system and earth. Value:
50% of the response value Z
an
Are the alarm LEDs lighting?
Alarm relays switched?
Yes
No
Check connections
Remove resistance
The iso1685FRM is connected
correctly and is functional
Alarm LEDs no longer lighting?
Alarm relays switched?
No
The iso1685FRM successfully
carries out a self test
Yes
No
Connect “(R)+Vs“ of the Analogue
Modbus Converter (M7024) to
“24 V“ of DC power supply 2, and
“(B)GND“ to “GND“
Analogue Modbus Converter:
Switch on the supply voltage
Содержание ISOMETER iso1685FR
Страница 6: ...6 ...
Страница 10: ...Important information 10 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Страница 14: ...Safety instructions 14 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Страница 42: ...Diagram for the calculation of Ze 42 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Страница 44: ...Information about the measuring method 44 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Страница 50: ...INDEX 50 iso1685FR M _D00002_02_M_XXEN 06 2017 ...
Страница 51: ...INDEX 51 iso1685FR M _D00002_02_M_XXEN 06 2017 ...