Technical data
84
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
Mains connection
Connection type........................................................................................................................ pluggable push-wire terminals
Connection, rigid/flexible........................................................................................................... 0.2…10 mm
2
/0.2…6 mm
2
Connection, flexible with ferrule, without/with plastic sleeve .................................................... 0.25...6 mm
2
/0.25...4 mm
2
Conductor sizes (AWG) ................................................................................................................................................... 24…8
Stripping length................................................................................................................................................................ 15 mm
Opening force............................................................................................................................................................ 90…120 N
Switching elements
Switching elements.................................................................................................................................3 changeover contacts:
K1 ................................................................................................................................................... insulation fault alarm 1
K2 ................................................................................................................................................... insulation fault alarm 2
K3 ......................................................................................................................................................................device error
Operating principle K1, K2 ....................................................................................................... N/C operation or N/O operation
Operating principle K3 ........................................................................................................ N/C operation, cannot be changed
Electrical endurance under rated operating conditions, number of cycles....................................................................100,000
Contact data acc. to IEC 60947-5-1:
Utilisation category .................................................................................................... AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Rated operational voltage .................................................................................................... 230 V / 230 V / 4 V / 10 V / 20 V
Rated operational current............................................................................................................ 5 A / 3 A / 1 A / 0.2 A / 0.1 A
Rated insulation voltage......................................................................................................................................................250 V
Minimum contact rating ....................................................................................................................... 1 mA at AC/DC ≥ 10 V
Environment/EMC
EMC...................................................................................................................................................................... IEC 61326-2-4
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) .........................................................................................................................................3K22
Transport (IEC 60721-3-2)...................................................................................................................................................2K11
Long-term storage (IEC 60721-3-1) .................................................................................................................................. 1K22
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3)..........................................................................................................................................3M11
Transport (IEC 60721-3-2)................................................................................................................................................... 2M4
Long-term storage (IEC 60721-3-1) ................................................................................................................................. 1M12
Deviation from the classification of climatic conditions:
Ambient temperature during operation iso1685DP, isoLR1685DP.................................................................. -40…+70 °C
Ambient temperature during operation isoHV1685D....................................................................................... -40…+55 °C
Ambient temperature transport ......................................................................................................................... -40…+80 °C
Ambient temperature long-term storage .......................................................................................................... -25 …+80 °C
Area of application.............................................................................................................................................≤ 3000 m AMSL