Device communication
71
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
9.1.7.3 Resetting error messages
Recorded errors are presented as alarm messages on the BMS bus.
The fault messages are reset via the device menu. If the fault continues to exist, the message
will be generated again. The error can also be reset by means of the acknowledgement com-
mand via the BMS bus.
9.1.7.4 Error codes
The following list contains all relevant error codes output via the BMS bus. The right-hand co-
lumn describes the relevant action to be taken in each case.
BMS
Error code
Component
Error
Action
0.30
Connection
Connection earth (E/KE)
Check connection
0.40
Connection
System connection (L1/+, L2/–)
Check connection
4.05
Parameter
Incorrect measurement profile selected
Change measure-
ment profile
7.63
System
Timeout system management
Restart the device
8.11
Hardware
Self test insulation measurement
Contact service
8.12
Hardware
Hardware measuring voltage source
Replace device
8.31
(isoxx1685DP
only)
Hardware
PGH: locating current too high
Replace device
8.32
(isoxx1685DP
only)
Hardware
PGH: locating current cannot be swit-
ched off
Replace device
8.42
Hardware
Supply voltage ADC
Replace device
8.43
Hardware
Supply v12 V
Replace device
8.44
Hardware
Supply voltage –12 V
Replace device
8.45
Hardware
Supply v5 V
Replace device
8.46
Hardware
Supply v3.3 V
Replace device
9.61
Parameter
Insulation measurement
Load and reparamete-
rise factory settings
9.63
(isoxx1685DP
only)
Parameter
Locating current injector
Load and reparamete-
rise factory settings
9.64
Parameter
Voltage measurement
Contact service