Commissioning
32
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
6.3.3
Setting the profile
In order to optimally adapt the insulation monitoring device to the system to be monitored,
select a profile that suits your system. For an overview of the profiles, refer to
. The Power circuits profile is suitable for most of the IT systems.
6.3.4
Setting response value
R
an1
for alarm 1
Set the prewarning response value here.
1
The response value range changes depending on the selected profile. See
.
1. The response values shown in the screenshots represent the default settings of an
iso1685DP device. The values differ depending on the device variant.
Profiles
x.x.x
• Power circuits
o Control
circuits
o High
capacitance
o Inverter>10 Hz
Commissioning
x.x
Please select
a profile
according to your
application.
x/xx
Alarm 1
x.x.x
40 kΩ
Min.
1 kΩ
Max.
10 MΩ
Commissioning
x.x
Please set
the response value
R(an1) for
Alarm 1.
x/xx