Technical data
75
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
12. Technical data
12.1 Device profiles
12.1.1
Power circuits
Main circuits without dynamic frequency changes. The universal profile is suitable for all systems
primarily with constant power frequencies and extraneous DC voltages. When using inverters and
dynamic frequency control, select Inverter > 10 Hz or Inverter < 10 Hz.
Diagram „Power circuits“
12.1.2
High capacitance
For systems with high leakage capacitances, e.g. ship applications, the impact of leakage capaci-
tances on the measuring result can be significantly reduced by selecting this profile.
Power frequency
System leakage
capacitance
Measuring
voltage
Response value range
DC, 15…460 Hz
0…150 μF
±50 V
iso1685DP: 200 Ω…1 MΩ
isoHV1685: 200 Ω…1 MΩ
isoLR1685DP: 20 Ω…100 kΩ
Power frequency
System leakage
capacitance
Measuring
voltage
Response value range
DC, 15…460 Hz
0…500 μF
±50 V
iso1685DP: 200 Ω…200 kΩ
isoHV1685: 200 Ω…200 kΩ
isoLR1685DP: 20 Ω…20 kΩ
1
10
100
0,1
1
10
100
1000
Ce 1μF
Ce 10μF
Ce 100μF
Response value Ran [k]
Res
an
[s]
!
(po":#$)