Tests and service
60
7.4.3
CT connection fault display (channel-related)
LED "ALARM 1" lights up. The common alarm relay switches. The
EDS460-DG displays:
The "CT fault" is displayed in the same way as "Display device error" on
page 58.
Possible causes:
Measuring current transformer defective
Power supply cable interrupted
Power supply cable short-circuited
7.4.4
Display "peak"
System-related faults may impair the insulation fault location process.
The EDS460-DG marks the faulty channels in the "Alarm/meas.values"
menu with "peak".
7.4.5
External alarm
LED "ALARM 2" lights up. The common alarm relay switches.
Possible causes:
Alarm message from an external device
Device failure
Fault
1/1
CT fault
Addr.: 2 Channel: 4
I(ds)
I(d)
1.
peak
<100mA