Operation
34
6.2.3
Carrying out a test
A test serves to check the device function (hardware components) of the
EDS. A test can be called in the following ways:
press the "TEST" button on the front panel of the EDS460-DG,
press an external test button connected to the EDS460-DG,
send a TEST command via the BMS bus,
call up the "TEST" function in the Control menu.
The EDS460-DG responds as follows:
LED "ALARM 1" and LED "ALARM 2" light.
All alarm relays switch (function can be deactivated, see page 48).
An alarm message is being sent to the BMS bus.
An entry is made in the history memory with the suffix "TEST".
The progress of the test is shown on the display.
The EDS460-DG will now display the maximum measured value
that can be detected for channel 12 (provided that the measuring
channel is functioning correctly). Press the "
T
" arrow key several
times to show that the other channels are functioning correctly.
Auto test:
TEST 12/12
Insulation fault
50 mA
Addr.: 2 Channel: 12