Menu mode: Operation and setting
67
MK2430_D00129_02_M_XXEN/09.2019
8.4.3.9
Settings menu 9: Interface
Sets the actual device address and indicates the transmission rate (baud rate) for the
connection to the internal BMS bus (RS-485).
1. Exit
Back to the main menu.
2. Addr.
Device address setting of this MK2430.
Addresses between 1 and 150 can be selected. The addresses 100 to
110 are intended for special applications (e.g. PC, OPC) and cannot
be used for devices.
Factory setting is address 001 (master).
3. Baud
The fixed preassigned baud rate is 9600 bit/s.
Change the corresponding device address if several MK2430 are connected to one
internal BMS bus. One MK2430 must have address 1 (master). All other MK2430 are
addressed in consecutive order: 2,3,4… There should be no gaps between addresses.
Only in this way the functionality of the system can be ensured (also refer to the "BMS
bus" manual).
Data exchange will only work between devices with the same baud rate.
1.Exit
2.Addr. RS485: 001
3.Baud RS485: 09600