Modbus process image in the memory of the COM461MT
57
COM461MT_D00011_00_M_XXEN/05.2013
7.5
Modbus control commands
Commands can be sent to BMS devices by an external application (e.g. data
display software).
Control via Modbus can be enabled or disabled on the "Settings" browser
menu.
Command structure
Writing to register:
To write use function code 0x10 "Write Multiple registers".
Start address: 0xFC00
Number: 4 registers
Always set all four registers (word 0xFC00…0xFC03) at the same time.
This statement also applies if individual registers remain unchanged.
If there is no external BMS bus, enter value "1" in this register.
If a BMS channel number is not required, enter value "0" (zero) in this
register.
Reading register:
To read use function code 0x04 "Read Input Registers".
Possible response in register "Status":
Write
Read
Word 0xFC00
0xFC01
0xFC02
0xFC03
0xFC04
External
BMS bus
address
Internal
BMS bus
address
BMS channel
Command
Status
0
Busy
Command is being processed.
1
Error
An error has occurred.
2
Ready
Command has been processed successfully.