6. Data access using Modbus/TCP protocol
Requests are sent to the Modbus/TCP server in the COM461MT using function
code FC4 (read input register). The server generates a function-related re-
sponse and sends it to the Modbus client.
6.1
Exception code
If a request cannot be answered for whatever reason, the server sends a so-
called exception code with which possible faults can be narrowed down.
Exception
code
Description
0x01 Impermissible
function
0x02 Impermissible
data
access
0x03 Impermissible
data
value
0x04
Slave device error
0x05
Acknowledgement of receipt (response delayed)
0x06
Request not accepted (repeat request, if necessary)
0x08
Memory: parity error
0x0A
Gateway path not available
0x0B Gateway
error