Installation, connection and commissioning
18
COM461MT_D00011_00_M_XXEN/05.2013
Terminal
Description
A1, A2
Connection to the supply voltage, 6 A fuse recommended,
two-pole fuses should be used on IT systems.
For UL and CSA applications, it is mandatory to use 5 A fuses
ETH1,
ETH2
Two connections for connection to a personal computer or to
the local network (hub, switch, router);
Connection using a CAT5 cable; internal Layer-2 switch with
cable autodetect.
A, B
Connection to the internal BMS bus with shielded cable (e.g.
J-Y(St)Y 2x0.8)
R
on/off
(A,B)
Switch for BMS bus termination. When the device is installed
at the end of the bus, set the terminating switch to "on".