Modbus process image in the memory of the COM461MT
34
COM461MT_D00011_00_M_XXEN/05.2013
7.2.4
Timestamp
The timestamp is set according to a datagram received from a transmitting
device.
7.2.5
C = Common alarm and D = Device lost (device failure)
The common alarm bit is set as soon as an alarm status from the respective
BMS device is detected.
The device error bit is set when communication with the respective BMS de-
vice is no longer possible.
Word 0x0A
0x0B
0x0C
0x0D
HiByte
LoByte
HiByte
LoByte
HiByte
LoByte
HiByte
LoByte
Year
YY
Month
MM
Day
DD
Hour
hh
Minute
mm
Second
ss
Re-
served
Word 0x0E
HiByte
LoByte
C
D
Common alarm, 1 byte:
LSB = 0 or 1
Device error, 1 byte:
LSB = 0 or 1