background image

General Information

Preliminary steps

1. 

Belimo actuators with NEMA 1 or NEMA 2 
ratings should be mounted indoors in a 
dry, relatively clean environment free from 
corrosive fumes.  If the actuator is mount-
ed outdoors, a protective enclosure must 
be used to shield the actuator. 

2. 

For new construction work, 

order dampers 

with extended shafts

.  Instruct the install-

ing contractor to allow space for mounting 
the Belimo actuator on the shaft.  

For replacement of existing gear train actua-

tors, there are two options:  

A. 

From a performance standpoint, it is 
best to mount the actuator directly 
onto the damper shaft. 

B. 

If the damper shaft is not accessible, 
mount the non-spring return actuator 
with a ZG-NMA or ZG-GMA crankarm 
kit, and a mounting bracket (ZG-100, 
ZG-101, ZG-103, ZG-104)

10 VDC

2 VDC

10 VDC

2 VDC

Direction of Rotation Switch 

Non-spring return actuators have a reversing 
switch on the cover.  Switch position indicates 
start point. For the non-spring return, with the 
switch in position 1, the actuator rotates clock-
wise with a decrease in voltage or current.  
With the switch in position 0, the actuator 
rotates counterclockwise with a decrease in 
voltage or current.  

The non-spring return rotates clockwise when the 
switch is in the 1 position and power is applied to 
wire #2.  When power is applied to wire #3 the 
actuator rotates counter clockwise.
Rotating the switch to 0 reverses the control logic.

During checkout, the switch position can be tem-
porarily reversed and the actuator will reverse its 
direction.  This allows the technician a fast and 
easy way to check the actuator operation without 
having to switch wires or change settings on the 
thermostat.  

When the check-out is complete, 

make sure the switch is placed back to its 
original position.

The …-S model actuators are equipped with an 
adjustable auxiliary switch used to indicate damp-
er position or to interface additional controls or 
equipment.  Switching positions can be set over 
the full 0 to 95° rotation simply by setting 
a switch on the actuator.

Auxiliary Switches

S2   S3

S1

S2   S3

S1

Switch Rating

Voltage 250 

VAC

Resistive load 

3 A

Inductive load 

0.5 A

Please refer to the appropriate product liter-
ature for detailed installation information.

Reference

•  Mounting Methods Guide
• Wiring Guide
•  Damper Application Guide

Mounting Installation Instructions

LM, NM, AM, GM

®

70569-00001 Re

v E

Содержание AMB series

Страница 1: ...ch in position 0 the actuator rotates counterclockwise with a decrease in voltage or current The non spring return rotates clockwise when the switch is in the 1 position and power is applied to wire 2...

Страница 2: ...11 16 1 5 6 to 7 ft lb AMB 1 2 to 1 05 3 8 to 11 16 1 5 6 to 7 ft lb AMQB 1 2 to 1 05 7 16 to 11 16 1 5 6 to 7 ft lb GMB 1 2 to 1 05 7 16 to 11 16 1 5 6 to 7 ft lb LMB standard clamp has max 5 8 diam...

Страница 3: ...8 between stop and clamp Tighten the two nuts on the universal clamp with a 8 10 or 12mm wrench see table column D on page 2 for required torque 5 Snap on the reflective position indicator Adjust end...

Страница 4: ...orque based on 4 in lb per sq ft Running Time Power Supply Power Consumption Feedback Airside Products 35 in lb 4 Nm Apprx 11 sq ft 45 in lb 5 Nm Apprx 11 sq ft 70 in lb 8 Nm Apprx 22 sq ft 90 in lb 1...

Страница 5: ...signal to 2 to 10 VDC up to 2 actuators may be connected in parallel Only connect common to neg leg of control circuits 1 2 3 4 5 Torque based on 4 in lb per sq ft Running Time Power Supply Power Cons...

Страница 6: ...4 VAC Transformer Blk 1 Common Wht 2 Hot Wht 3 Y1 Input Pnk 4 Y2 Input Org 5 U Output 2 to 10V 1 3 6 4 2 A B 8 9 Notes W399 Provide overload protection and disconnect as required Actuators may be conn...

Страница 7: ...r may also be powered by 24 VDC Actuators and controller must have separate transformers Consult controller instruction data for more detailed installation information Resistor value depends on the ty...

Страница 8: ...erations Mechanical Features Mechanical Angle of Rotation Limiting The adjustable stops are needed when there is no damper stop or if you want the damper to stop rotating before it reaches its stops T...

Отзывы: