Technical Manual
LioN-Link DeviceNet
Subject to change without notice!
Version 1.0 / June 2010
Page 15 of 27
6.
Configuring
The configuration of the LioN-Link BusHead described on the following pages was accomplished with the help of the
RSNetWorx
TM
-software from Rockwell Automation, Inc. In case of using a control system from another controller supplier
please attend to the associated documentation.
6.1.
Node address
For the direct setting of the DeviceNet node address two rotary switches are used, which are
located above the two M12 LioN-Link connectors behind a transparent cover. The switches for
the ten’s and unit position of the address are marked. The adjusted address is accepted when
the power supply is switched on. Therefore the power supply must be interrupted shortly after
a change of the address, so that the BusHead accepts the new address.
The node address is adjusted with the rotary switches at the front. The valid
range of values is from 1 to 63. If a node address is set that is not within the
limits, the address 63 is used automatically.
6.2.
Data rate
The DeviceNet BusHead 0940 DSL 601 supports all data rates that are released by the ODVA. These are 125 kBit/s, 250 kBit/s
and 500 kBit/s. The Bushead automatically detects the used data rate, a manual or fixed setting of the data rate is not possible.
6.3.
EDS configuration file
For the configuration and parameterization of the BusHead in the control system an EDS-file is required. This EDS-file can be
downloaded from our homepage under
http://www.beldensolutions.com/en/Service/Downloadcenter/Software_Lumberg/index.phtml
.
On request the EDS-file is also mailed by the support team.
The EDS-file that is being received has a modular structure. For optimal performance the configuration software
should support the use of modular EDS-files. If the configuration software cannot use modular EDS-files try to
use the file “00_0940 DSL 601.eds” from the list of supplied EDS-files for configuration. In this case the number
of producer and consumer bytes for the Bushead has to be self-calculated.
In
RSNetWorx select Tools – EDS Registry Wizard to register and install the EDS-file. The LioN-Link system with the DeviceNet
BusHead is displayed afterwards in the hardware list.