Technical Manual 

 

 

LioN-Link DeviceNet 

 

Subject to change without notice! 

 

Version 1.0 / June 2010 

 

 

Page 15 of 27 

 

6.

 

Configuring 

 

The configuration of the LioN-Link BusHead described on the following pages was accomplished with the help of the 
RSNetWorx

TM

-software from Rockwell Automation, Inc. In case of using a control system from another controller supplier 

please attend to the associated documentation. 
 

 

6.1.

 

Node address 

 

For the direct setting of the DeviceNet node address two rotary switches are used, which are 
located above the two M12 LioN-Link connectors behind a transparent cover. The switches for 

the ten’s and unit position of the address are marked. The adjusted address is accepted when 
the power supply is switched on. Therefore the power supply must be interrupted shortly after 

a change of the address, so that the BusHead accepts the new address. 
 

 

The node address is adjusted with the rotary switches at the front. The valid 

range of values is from 1 to 63. If a node address is set that is not within the 

limits, the address 63 is used automatically. 

 

 
 

6.2.

 

Data rate 

 

The DeviceNet BusHead 0940 DSL 601 supports all data rates that are released by the ODVA. These are 125 kBit/s, 250 kBit/s 
and 500 kBit/s. The Bushead automatically detects the used data rate, a manual or fixed setting of the data rate is not possible. 

 
 

6.3.

 

EDS configuration file 

 

For the configuration and parameterization of the BusHead in the control system an EDS-file is required. This EDS-file can be 
downloaded from our homepage under 

 

http://www.beldensolutions.com/en/Service/Downloadcenter/Software_Lumberg/index.phtml

 
On request the EDS-file is also mailed by the support team. 

 

The EDS-file that is being received has a modular structure. For optimal performance the configuration software 

should support the use of modular EDS-files. If the configuration software cannot use modular EDS-files try to 

use the file “00_0940 DSL 601.eds” from the list of supplied EDS-files for configuration. In this case the number 
of producer and consumer bytes for the Bushead has to be self-calculated. 

 
 

In 

RSNetWorx select Tools – EDS Registry Wizard to register and install the EDS-file. The LioN-Link system with the DeviceNet 

BusHead is displayed afterwards in the hardware list. 

 
 

Содержание Lumberg LioN-Link 0940 DSL 601

Страница 1: ...Technical Manual 0940 DSL 601...

Страница 2: ...ports M12 plug socket 5 pole A coded 12 5 1 2 Power supply connector for the BusHead M12 plug 5 pole 12 5 1 3 Link system connector M12 socket 5 pole 12 5 2 Intermediate power supply feed on LioN Link...

Страница 3: ...olling 23 6 7 2 Change of State 23 7 Operation of the BusHead 24 7 1 Commissioning 24 7 2 Exchange of I O modules 24 7 3 Bus interruptions and restart 24 7 4 Diagnostics 25 7 5 System expansion 25 8 T...

Страница 4: ...s please do not hesitate to contact us We will be glad to be at your disposal at any time Belden Deutschland GmbH Lumberg Automation Im Gewerbepark 2 58579 Schalksmuehle Germany Tel 49 0 23 55 5044 00...

Страница 5: ...ferences in the residential area In this case the operator can be required to accomplish appropriate measures The proper and safe function of the product requires an appropriate transport storage inst...

Страница 6: ...ce as well as their knowledge of the relevant standards have the same level of knowledge as after a technical education due to an activity in a comparable area for several years Modifications to the h...

Страница 7: ...distance between two link participants is arbitrary The permissible overall length for each line may not be exceeded however Using the maximum expansion of the system an additional feed of the power s...

Страница 8: ...d with M12 socket straight 5 pole A coded 0935 253 106 M Connecting cable for DeviceNet and LioN Link line single ended with M12 socket angled 5 pole A coded 0935 253 107 M Connecting cable for Device...

Страница 9: ...ge without notice Version 1 0 June 2010 Page 9 of 27 T connectors 0906 UTP 101 T connector for daisy chaining the power supply Pay attention to the current load 0906 UTP 104 T connector for additional...

Страница 10: ...Technical Manual LioN Link DeviceNet Subject to change without notice Version 1 0 June 2010 Page 10 of 27 4 Mounting 4 1 Outer dimensions...

Страница 11: ...a flat washer according to DIN 125 has to be used Important note For the derivation of interference currents and or for the EMC stability the module provides a metal grounding sheet It is necessary t...

Страница 12: ...5 pole Colour code of the connector orange Connector Pin Signal Function 1 Drain Shield 2 24 V Power supply 3 GND 0 V Power supply 4 CAN_H Data signal DeviceNet IN OUT 5 CAN_L Data signal Connector Pi...

Страница 13: ...dules During the planning of a machine or a plant it has to be considered that starting from certain cable lengths an intermediate power supply feed for the electronics and sensors of the I O modules...

Страница 14: ...nk line a calculation table as a Microsoft Excel sheet is available under http www beldensolutions com en Service Downloadcenter Software_Lumberg index phtml The table determines the voltage drop on t...

Страница 15: ...s the address 63 is used automatically 6 2 Data rate The DeviceNet BusHead 0940 DSL 601 supports all data rates that are released by the ODVA These are 125 kBit s 250 kBit s and 500 kBit s The Bushead...

Страница 16: ...tion Adapter 6 4 1 Configuration of the LioN Link system Click on the part description of the BusHead 0940DSL601 in the hardware list Move the system to the DeviceNet line The DeviceNet node address a...

Страница 17: ...cording to their physical installation Start with the first module at line 1 next to the BusHead Then insert the subsequent I O Modules of line 1 followed by those of line 2 Observe the correct order...

Страница 18: ...elect the button Edit I O Parameters or doubleclick on the device name of the LioN Link system in the scanlist to edit the I O parameters Select desired communication mode and the number of input and...

Страница 19: ...1 0 June 2010 Page 19 of 27 6 5 Parameter settings Access to the parameter settings of the BusHead and the I O modules of the LioN Link system can be obtained by a doubleclick on the BusHead or the I...

Страница 20: ...revision The firmware version of the BusHead can be read out with the configuration tool Access is obtained using the class 102 instance 01 and the attribute 03 3 Count of modules line 1 This paramete...

Страница 21: ...ts operation only if the actual and stored configuration are identical Access is obtained using the class 102 instance 01 and the attribute 07 8 Reset Module Configuration This parameter is editable i...

Страница 22: ...nt Process data The process data are divided into consumer output data and producer input data The process data are transferred as a block according to the DeviceNet specification 6 6 1 Process data o...

Страница 23: ...an incorrect status 0 I O module with number 1 16 is configured correctly Please consider that only the first detected configuration error can be reported 6 6 2 Process data of the I O modules The pro...

Страница 24: ...module only In this case no diagnostics of the actuator power is indicated or evaluated 7 3 Bus interruptions and restart During an interruption of the bus line of one or both LioN Link lines the MS...

Страница 25: ...bytes of an I O module can be obtained by the class 101 The instance is built up according to the respective position of the I O module on the LioN Link line starting with the first I O module in LioN...

Страница 26: ...e power supply for the fieldbus interface Rated voltage US 24 V DC Voltage range 11 30 V DC Current consumption typ 10 mA Reverse polarity protection yes Operation indicator US LED green Connection vi...

Страница 27: ...dules permuted red green alternating flashing Restart of line 1 and or line 2 S1 S2 off Line 1 and or line 2 not used no I O module connected green Ethernet connection to another participant exists ye...