4.1. Connection to power supply
The voltage drop caused by the electronics in the device is approx. 6 VDC. This must be taken into account when
dimensioning the power supply. The limit values are calculated as follows:
Minimum operating voltage:
U
B min
=
U
min MU
+ 6 V
Maximum operating voltage:
U
B max
=
U
max MU
+ 6 V
Key:
U
min MU
= minimum operating voltage of installed 2-wire transducer
U
max MU
= maximum operating voltage of installed 2-wire transducer
4.2. Power supply for METPOINT
®
DPM SD21 2-wire transducer
4.3. Power supply for METPOINT
®