23 / 172 EN
Split Type Air Conditioner / User Manual
4 Installation
C
If the wall is made of brick,
concrete, or similar material, drill
5mm-diameter (0.2in-diameter)
holes in the wall and insert the
sleeve anchors provided. Then
secure the mounting plate to the
wall by tightening the screws
directly into the clip anchors.
Step 3: Drill wall hole for connective piping
1. Determine the location of the wall hole based
on the position of the mounting plate. Refer to
Mounting Plate Dimensions.
2. Using a 65mm (2.5in) or 90mm (3.54in)
(depending on models) core drill, drill a hole in
the wall. Make sure that the hole is drilled at a
slight downward angle, so that the outdoor end
of the hole is lower than the indoor end by about
5mm to 7mm (0.2-0.275in). This will ensure
proper water drainage.
3. Place the protective wall cuff in the hole. This
protects the edges of the hole and will help seal
it when you finish the installation process.
A
CAUTION!
When drilling the wall
hole, make sure to avoid wires,
plumbing, and other sensitive
components.
Wall
Indoor
Outdoor
5-7 mm (0.2-0.275in)
Indoor
Wall
Outdoor
5-7 mm
(0.2-0.275in)
4.2.2 Mounting plate dimensions
Different models have different mounting plates.
For the different customization requirements,
the shape of the mounting plate may be slightly
different. But the installation dimensions are the
same for the same size of indoor unit. See Type A
and Type B for example:
Correct orientation of Mounting Plate
Correct orientation of Mounting Plate
Type A
Type B
Type A
Type B
101mm (4in)
179mm (7.05in)
136mm (5.35in)
37mm (1.45in)
290mm (11.4in)
49mm (1.95in)
Right rear wall
hole 65mm (2.5in)
Indoor unit outline
722mm (28.45in)
49mm (1.95in)
Left rear wall
hole 65mm (2.5in)
Model A
348.4mm (13.7in)
Left rear wall hole
65mm (2.5in)
Right rear wall
hole 65mm (2.5in)
Indoor unit outline
101mm (4in)
348.4mm (13.7in)
179mm (7.05in)
136mm (5.35in)
722mm (28.45in)
Model A
49mm (1.95in)
37mm (1.45in)
49mm (1.95in)
290mm (11.4in)
228mm (8.98in)
229mm (9.01in)
401mm (15.78in)
126mm (4.96in)
42mm (1.65in)
297mm (11.7in)
Left rear wall
hole 65mm (2.5in)
Right rear wall
hole 65mm (2.5in)
Indoor unit outline
802mm (31.6in)
58mm (2.28in)
47mm (1.85in)
Model B
Left rear wall hole
65mm (2.5in)
Right rear wall hole
65mm (2.5in)
Indoor unit outline
228mm (8.98in)
401mm (15.78in)
229mm (9.01in)
126mm (4.96in)
802mm (31.6in)
Model B
58mm (2.28in)
42mm (1.65in)
47mm (1.85in)
297mm (11.7in)
Содержание BEHPH 090
Страница 2: ...ENGLISH 3 56 ITALIANO 57 114 FRANÇAIS 115 172 CONTENTS V2110002 AB UM ...
Страница 152: ...152 172 FR Climatiseur fixe Notice d utilisation 5 Raccordement de la tuyauterie de réfrigérant ...
Страница 172: ...Arçelik A Ş Karaağaç Caddesi No 2 6 34445 Sütlüce İstanbul Türkiye www beko com ...
Страница 173: ...User Manual 10M 8505543200 4921 01 EN IT FR Remote Control ...
Страница 174: ...ENGLISH 3 19 ITALIANO 20 37 FRANÇAIS 38 56 CONTENTS V2110002 AB RC ...
Страница 228: ...Arçelik A Ş Karaağaç Caddesi No 2 6 34445 Sütlüce İstanbul Türkiye www beko com ...