4 / 64 EN
Air conditioner / User Manual
•
To guarantee the unit work normally, please read the manual
carefully before installation, and try to install strictly according to
this manual.
•
Do not let air enter the refrigeration system or discharge refrigerant
when moving the air conditioner.
•
Properly ground the air conditioner into the earth.
•
Check the connecting cables and pipes carefully, make sure they are
correct and firm before connecting the power of the air conditioner.
•
There must be an air-break switch.
•
After installing, the consumer must operate the air conditioner
correctly according to this manual, keep a suitable storage for
maintenance and moving of the air conditioner in the future.
•
Fuse of indoor unit: T 3.15A 250V.
•
For 7k~12k models, fuse of outdoor unit: T 15A 250V or T 20A 250V.
•
For 14k~18K models, fuse of outdoor unit: T 20A 250V.
•
For 21K~30k models, fuse of outdoor unit: T 30A 250V.
•
A residual current device (RCD) with the rating of above 10mA shall
be incorporated in the fixed wiring according to the national rule.
A
Warning:
Risk of electric shock can cause injury or death:
Disconnect all remote electric power supplies before
servicing.
•
The maximum length of the connecting pipe between the indoor
unit and outdoor unit should be less than 5 meters. It will affect
1
Safety instructions