Air conditioner / User Manual
21 / 64 EN
Location for installing outdoor unit
•
Where it is convenient to install and well ventilated.
•
Avoid installing it where flammable gas could leak.
•
Keep the required distance apart from the wall.
•
The distance between Indoor and outdoor unit should
be 5 meters and can go up to maximum 15 meters with
additional refrigerant charge.
•
Keep the outdoor unit away from greasy dirt, vulcanization
gas exit.
•
Avoid installing it by the roadside where there is a risk of
muddy water.
•
A fixed base where it is not subject to increased operation
noise.
•
Where there is not any blockage of the air outlet.
•
Avoid installing under direct sunlight, in an aisle or sideway,
or near heat sources and ventilation fans. Keep away from
flammable materials, thick oil fog, and wet or uneven
places.
Outdoor unit
Pipe length is
15 meters max.
Heigh
t should be
less than 5m
Indoor unit
Model
Max. allowable
tubing length at
shipment (m)
Limit of tubing
length (m)
Limit of elevation
difference H (m)
Required amount
of additional
refrigerant (g/m)
7K~18K
5
15
5
20
21K~25K
5
15
5
30
30K
5
15
5
40
If the height or pipe length is out of the scope of the table, please consult the merchant.