26 / 64 EN
Air conditioner / User Manual
C
Note:
The figures in this manual are based on the external view of a standard model.
Consequently, the shape may differ from that of the air conditioner you have selected.
A
Warning:
1. Never fail to have an individual power circuit specifically for the air conditioner. As for
the method of wiring, refer to the circuit diagram posted on the inside of the access
door.
2. Confirm that the cable thickness is as specified in the power source specification.
3. Check the wires and make sure that they are all tightly fastened after cable
connection.
4. Be sure to install an earth leakage circuit breaker in wet or moist areas.
Cable specifications
Capacity
(Btu/h)
Power cord
Power connecting cord
Type
Normal cross
- sectional area
Type
Normal cross
- sectional area
7K~12K
H07RN-F
1.0/1.5mm
2
×3
H07RN-F
1.0/1.5mm
2
×5
7K*~12K*
H05VV-F
1.0/1.5mm
2
×3
H07RN-F
1.0/1.5mm
2
×4
14K~18K
H07RN-F
1.5mm
2
×3
H07RN-F
1.5mm
2
×5
14K*~18K*
H05VV-F
1.5/2.5mm
2
×3
H07RN-F
1.5/2.5mm
2
×4
21K~30K
H07RN-F
2.5mm
2
×3
H07RN-F
0.75mm
2
×4
H07RN-F
2.5mm
2
×3
H07RN-F
2.5mm
2
×5
21K*~30K*
H05VV-F
2.5mm
2
×3
H07RN-F
2.5mm
2
×4
21K**~24K** H05VV-F
1.5mm
2
×3
H07RN-F
1.5mm
2
×4
C
Note:
1. K* means the power supply of this model comes from indoor unit.
2. K** indicates indoor power supply unit model with power line and plug.
3. For 14K*~18K* models under Tropical (T3) Climate condition, the normal cross-
sectional area of Power cord and Power connecting cord is 2.5mm
2
×4.
8
Installation instructions