EN
Installation and operating manual
35 METPOINT
®
SF13
Setup
→
4 - 20 mA
→
Error Current
On this screen, you can enter the error signal to be sent by the
current output in the event of a fault.
•
2 mA = sensor fault / system error
•
22 mA = sensor fault / system error
•
None = output according to Namur (3.8 mA ... 20.5 mA)
< 4 mA to 3.8 mA = value below measuring range
> 20 mA to 20.5 mA = value above measuring range
Confirm your entry by pressing the >>ENTER<< button.
6.9. Info
Setup
→
Info
This screen shows device information.
Press "Details" to view the calibration conditions.
6.10. MBus
6.10.1. Default communication settings
Primary address*:
1
ID:
Serial number of sensor
Baud rate*:
2400
Medium*:
Gas
6.10.2. Transferred values
Value 1 with [Unit]*:
Flow [m³/h]
Value 2 with [Unit]*:
Consumption [m³]
Value 3 with [Unit]*:
Velocity [m/s]
Value 4 with [Unit]*:
Gas temperature [°C]
* these values can be factory-set or changed on request.