4.4.3. Galvanically isolated pulse output
Connection by means of plug-type connector B.
Connection diagram for METPOINT
®
SF13 and METPOINT
®
BDL compact (analog board)
METPOINT
®
FLM SFxx
METPOINT
®
BDL
compact
Analogboard
BROWN
q
BLACK
GREY
BLUE
1
4
5
3
Impuls
V
U
+
V
U
+
V
U
-
V
-
U
V
1
2
3
4
5
6
7
8
9
R
Pin assignment - sensor
Function
Wire colour Pin assignment - BDL compact
PIN-1
+ U
V
not assigned
brown
PIN-4
Pulse
Pulse
black
PIN-1
+ U
V
PIN-5
Pulse
Pulse
grey
PIN-8
(+) V - PT
PIN-3
- U
V
not assigned
blue
PIN-2
not assigned
white
4.5. Modbus termination
If the METPOINT
®
FLM is the last device in the Modbus system, it must be terminated. The sensor is equipped with a built-in
terminator. To terminate the device, loosen the 2 top setscrews at the housing. lift off the lid and set the DIP switch (1) to ON.
When closing the sensor housing, ensure that the housing gasket is correctly installed.