10.3.8  Access Setpoint:  AcSP

This function controls the parameters in a separate
menu which provides direct access to the alarm
setpoints when the transmitter is in the display
mode i.e. when it is displaying temperature.  See
section 10.4 for a full description.    This menu
allows an operator to adjust the two alarm
setpoints without having access to the Programme,
Trim or Alarm Menus.  A separate security code
may be defined to prevent unauthorised access.

This separate direct access menu is enabled and a
separate security code entered from the 'AcSP'
function in the Programme Menu - see Fig 11.  To
change the menu parameters select 'AcSP' from
the Programme Menu and press 

P

  which will

display the enable prompt 'EnbL'.  Press 

P

 again to

reveal if the direct access menu is 'On' or 'OFF'.
The 

Up

 or 

Down

 buttons will toggle the display

between the two conditions.  

If 'OFF' is selected, the operator will not have
access to the setpoints from the display mode.
Return to the 'AcSP' prompt in the main menu by
pressing

 E

 twice.  

If 'On' is selected, the operator will have direct
access to the alarm setpoints from the display
mode via a separate optional security code.   To
define the four digit numerical code press 

P

 to

return to the 'Enbl' prompt followed by the 

Up

 or

Down

 button to select the access code prompt

'AcCd'.   Pressing 

will reveal the current security

code.  Each digit of the code may be changed by
operating the 

Up

 and 

Down

 push-buttons, and the

P

 button to move to the next digit.  When the

required code has been entered, press 

E

 twice to

return to the 'AcSP' prompt in the Programme
Menu.

Code 0000 will disable the security code allowing
direct access to the setpoints by pressing the

  P

and 

Up

 buttons simultaneously.

New instruments are supplied with this function
disabled and the security code set to 0000

10.4  Adjusting the alarm setpoints from the

   display mode.

Access to the alarm setpoint when the BA574C
transmitter is in the display mode is obtained by
operating the 

P

 and 

Up

 push-buttons simultane-

ously - see Fig 12.   If the setpoints are not
protected by a security code the alarm setpoint one
'SP1' will be displayed.  If the setpoints are
protected by a security code, 

'COdE' will be displayed first.  Pressing 

P

 again will

enable the alarm security code to be entered digit
by digit using the 

Up

 and 

Down

 buttons to change

the flashing digit, and the 

P

  push-button to move to

the next digit.   If the correct code is entered press-
ing 

E

 will cause alarm setpoint one 'SP1' to be

displayed.  Pressing the 

Up

 or 

Down

 button will

toggle the display between 'SP1' and 'SP2'.  

Fig 12  Setpoint adjustment from display mode

If an incorrect code is entered, or a button is not
pressed for ten seconds, the transmitter will
automatically return to the display mode. 

To adjust an alarm setpoint select 'SP1' or 'SP2'
and press 

P

  which will reveal the current setting.

Each digit of the setpoint may be adjusted using the

Up

 and 

Down

 push-buttons, and the 

button to

move to the next digit.  When the required setpoint
has been entered, pressing  

E

  will return the

display to the 'SP1' or 'SP2' prompt from which the
other setpoint may be selected, or the transmitter
may be returned to the display mode by pressing 

E

again.

      25

Содержание BA574C

Страница 1: ...BA574C field mounting indicating temperature transmitter issue 4 Issue 4 26th September 2008...

Страница 2: ...Voltage input reference 5 8 3 3 wire RTD reference 5 8 4 4 wire RTD reference 5 8 5 Output current reference 6 Trim menu 6 1 Calibration procedure using Trim menu 6 2 Periodic re calibration using Tr...

Страница 3: ...n 5 you will find information on setting up for Section 5 3 Themocouple input Section 5 4 Resistance thermometer input Section 5 5 Voltage inputs A word of warning Section 5 8 explains how you can cal...

Страница 4: ...4...

Страница 5: ...and controls the 4 20mA output current The transmitter and the optional alarms are powered from the 4 20mA current loop but the optional display backlight requires a separate supply Each time power is...

Страница 6: ...must have an output greater than 15 2V 4 INSTALLATION 4 1 Location The BA574C indicating transmitter can be supplied in either a glass reinforced polyester GRP or an epoxy painted aluminium enclosure...

Страница 7: ...ation to be performed against the internal transmitter refer ences The Trim Menu enables the transmitter display and the 4 20mA output current to be calibrated against an external standard such as a v...

Страница 8: ...ermocouple and resistance thermometer inputs The BA574C transmitter will always display sensor temperature Programming allows the display to be in degrees Centigrade or Fahren heit and for the display...

Страница 9: ...the output is 4mA and SPAn the display at which the output is 20mA See section 5 6 COdE Security code Defines a four digit numeric code which must be entered to gain access to the programme and the t...

Страница 10: ...10...

Страница 11: ...11...

Страница 12: ...is only available when the transmitter is displaying temperature in o C When o F is selected the resolution is always one degree To check or change the display resolution select rESn from the sub menu...

Страница 13: ...l point can be positioned between any of the display digits or it may be absent After selecting voltage input from the InPut menu press P to reveal the d P sub menu Press P again to display the curren...

Страница 14: ...ay can be changed by pressing the Up or Down buttons When the first digit is correct pressing P will transfer control to the next digit When the least significant digit has been adjusted press E to re...

Страница 15: ...is a ten second time out on password entry Pressing E will then give access to the sub menu containing the four refences 5 8 2 Voltage input reference U IP With the BA574C input terminals connected t...

Страница 16: ...nsmitter to be adjusted using an external voltage resistance or temperature calibrator For maximum accuracy the complete loop including the thermocouple or resistance thermometer may be calibrated by...

Страница 17: ...shown on the DVM or other instrument When correct press the E button to store the trim correction in perma nent memory and return the BA574C transmitter to the SPAn prompt This completes re calibratio...

Страница 18: ...u Step 8 Input open circuit drive Using the Up or Down button select burn from the sub menu and press P to reveal the current status Select uP using the Up or Down button and press E three times to re...

Страница 19: ...sh P which will cause the transmitter to display the thermocouple temperature Adjust the display with the Up and Down buttons until it is 240 0 Note Immediately the Up or Down button is operated the a...

Страница 20: ...ammable on site a single spare transmitter or electronic assembly may therefore be used to replace any instrument which fails We recommend that suspect instruments are returned to BEKA associates or o...

Страница 21: ...nt panel 10 0 ALARMS The BA574C can be supplied with two solid state single pole alarm outputs Each output may be programmed as a high or low alarm with a normally open or a normally closed output Fig...

Страница 22: ...he operating mode See section 10 3 2 HI LO Alarm function Defines whether the alarm has a high or low function See section 10 3 3 no nc Normally open or normally closed output Determines whether the s...

Страница 23: ...23 Fig 11 Programme structure for optional alarms...

Страница 24: ...m output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc p...

Страница 25: ...e has been entered press E twice to return to the AcSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons si...

Страница 26: ...tter is installed in a poorly illuminated area The backlight is segregated from the measuring circuit and may be powered from any supply with an output between 18 and 30V dc as shown in Fig 13 If the...

Отзывы: