If the display does not correspond with the input
calibrator or the temperature of the primary
element, operate the 

Up

 or 

Down

 button until the

transmitter display is correct.  Immediately the 

Up

or 

Down

 button is operated the annunicator in the

top left hand corner of the display will be activated
to warn that any changes in the input signal will be
ignored while this display correction is being made.

When the transmitter display is correct, press 

P

which will lock the transmitter display and, after
briefly displaying 'Ent', allow the 4/20mA output
current to be trimmed using the 

Up

 or 

Down

 push-

button.  The output current should be measured
with an accurate DVM or another instrument within
the loop.  Operate the 

Up

 or 

Down

 buttons until the

required output current is shown on the DVM or
other instrument. When correct, press the 

E

 button

to store the trim correction in permanent memory
and return the BA574C transmitter to the 'ZEro'
prompt.  This completes re-calibration of the
BA574C transmitter at minimum input.

The transmitter should now be re-calibrated at
maximum input by selecting the 'SPAn' sub-menu
and adjusting the calibrator to simulate maximum
input, or raising the primary element to maximum
temperature.  With 'SPAn' displayed, pressing the

push-button will cause the temperature display to

return.  If the display does not correspond with the
input calibrator or the temperature of the primary
element, operate the 

Up

 or 

Down

 buttons until the

transmitter display is correct.  Immediately the 

Up

or 

Down

 button is operated the annunicator in the

top left hand corner of the display will be activated
to warn that any changes in the input signal will be
ignored while this display correction is being made.

When the transmitter display is correct, press 

P

which will lock the transmitter display and, after
briefly displaying 'Ent', allow the 4/20mA output
current to be trimmed using the 

Up

 or 

Down

 push-

button.  Again the output current should be
measured with an accurate DVM or another instru-
ment within the loop.  Operate the 

Up

 or 

Down

buttons until the required output current is shown on
the DVM or other instrument. When correct, press
the 

E

 button to store the trim correction in perma-

nent memory and return the BA574C transmitter to
the 'SPAn' prompt.   This completes re-calibration
of the BA574C transmitter at maximum input.

When calibrating the BA574C using the Trim Menu
both the zero and span must be adjusted.

The Trim Menu contains a clear function which
enables the small calibration correction made with
the 'ZEro' and 'SPAn' sub-menus to be removed.
To clear the corrections select 'CLr' from the trim
menu and press

 P.  

The display will show 'Ent' for a

short while and then return to the 'CLr' prompt.

6.2  Periodic re-calibration using Trim Menu

The Trim Menu is the best way of making small
calibration adjustments to compensate for any long
term drift which may occur.   Initially an annual
check is recommended to achieve maximum
accuracy, although less frequent checks will usually
produce acceptable results.

If the BA574C internal references are used to make
frequent calibration changes, we recommend that
these references should be initially checked once
per year as described in sections 5.8.1 to 5.8.5   If
the BA574C is always calibrated with an external
reference, such as a voltage source using the Trim
Menu, it will not be necessary to check the internal
reference. 

7.  CALIBRATION EXAMPLE

In this example a BA574C is required to display
with maximum resolution the temperature of a type
J thermocouple, and to transmit a 4/20mA signal
representing -10 to 240

o

C.  If the thermocouple

breaks the 4/20mA output current is to rise to full
scale.   The current security code is 1209.

The example is divided into two sections.  Steps 1
to 10 explain how to condition the transmitter and to
calibrate the 4/20mA output using the internal
references.  This will produce acceptable accuracy
for most applications, but will not compensate for
errors in the thermocouple or load connected to the
4/20mA output.  Steps 11 to 13 describe how the
Trim Menu may be used to calibrate the complete
loop and to compensate for thermocouple errors.

Step 1

Initialisation

When power is applied to the loop the
BA574C will automatically perform the
initialisation routine described in section
2, and then display and transmit the
thermocouple temperature using the
existing calibration information.

      17

Содержание BA574C

Страница 1: ...BA574C field mounting indicating temperature transmitter issue 4 Issue 4 26th September 2008...

Страница 2: ...Voltage input reference 5 8 3 3 wire RTD reference 5 8 4 4 wire RTD reference 5 8 5 Output current reference 6 Trim menu 6 1 Calibration procedure using Trim menu 6 2 Periodic re calibration using Tr...

Страница 3: ...n 5 you will find information on setting up for Section 5 3 Themocouple input Section 5 4 Resistance thermometer input Section 5 5 Voltage inputs A word of warning Section 5 8 explains how you can cal...

Страница 4: ...4...

Страница 5: ...and controls the 4 20mA output current The transmitter and the optional alarms are powered from the 4 20mA current loop but the optional display backlight requires a separate supply Each time power is...

Страница 6: ...must have an output greater than 15 2V 4 INSTALLATION 4 1 Location The BA574C indicating transmitter can be supplied in either a glass reinforced polyester GRP or an epoxy painted aluminium enclosure...

Страница 7: ...ation to be performed against the internal transmitter refer ences The Trim Menu enables the transmitter display and the 4 20mA output current to be calibrated against an external standard such as a v...

Страница 8: ...ermocouple and resistance thermometer inputs The BA574C transmitter will always display sensor temperature Programming allows the display to be in degrees Centigrade or Fahren heit and for the display...

Страница 9: ...the output is 4mA and SPAn the display at which the output is 20mA See section 5 6 COdE Security code Defines a four digit numeric code which must be entered to gain access to the programme and the t...

Страница 10: ...10...

Страница 11: ...11...

Страница 12: ...is only available when the transmitter is displaying temperature in o C When o F is selected the resolution is always one degree To check or change the display resolution select rESn from the sub menu...

Страница 13: ...l point can be positioned between any of the display digits or it may be absent After selecting voltage input from the InPut menu press P to reveal the d P sub menu Press P again to display the curren...

Страница 14: ...ay can be changed by pressing the Up or Down buttons When the first digit is correct pressing P will transfer control to the next digit When the least significant digit has been adjusted press E to re...

Страница 15: ...is a ten second time out on password entry Pressing E will then give access to the sub menu containing the four refences 5 8 2 Voltage input reference U IP With the BA574C input terminals connected t...

Страница 16: ...nsmitter to be adjusted using an external voltage resistance or temperature calibrator For maximum accuracy the complete loop including the thermocouple or resistance thermometer may be calibrated by...

Страница 17: ...shown on the DVM or other instrument When correct press the E button to store the trim correction in perma nent memory and return the BA574C transmitter to the SPAn prompt This completes re calibratio...

Страница 18: ...u Step 8 Input open circuit drive Using the Up or Down button select burn from the sub menu and press P to reveal the current status Select uP using the Up or Down button and press E three times to re...

Страница 19: ...sh P which will cause the transmitter to display the thermocouple temperature Adjust the display with the Up and Down buttons until it is 240 0 Note Immediately the Up or Down button is operated the a...

Страница 20: ...ammable on site a single spare transmitter or electronic assembly may therefore be used to replace any instrument which fails We recommend that suspect instruments are returned to BEKA associates or o...

Страница 21: ...nt panel 10 0 ALARMS The BA574C can be supplied with two solid state single pole alarm outputs Each output may be programmed as a high or low alarm with a normally open or a normally closed output Fig...

Страница 22: ...he operating mode See section 10 3 2 HI LO Alarm function Defines whether the alarm has a high or low function See section 10 3 3 no nc Normally open or normally closed output Determines whether the s...

Страница 23: ...23 Fig 11 Programme structure for optional alarms...

Страница 24: ...m output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc p...

Страница 25: ...e has been entered press E twice to return to the AcSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons si...

Страница 26: ...tter is installed in a poorly illuminated area The backlight is segregated from the measuring circuit and may be powered from any supply with an output between 18 and 30V dc as shown in Fig 13 If the...

Отзывы: