3.  Application

3.1 Transmitter loops

BA527C and BA528C indicators may be
connected in series with any 4/20mA current loop
providing the loop can tolerate the additional 1.1V
required to operate the indicator. Fig 2 illustrates a
typical application in which a BA527C or BA528C
indicator is connected in series with a 2-wire
transmitter.

Fig 2 BA527C or BA528C in a transmitter loop

The sum of the maximum voltage drop of all the
components must be less than the minimum power
supply voltage.

Minimum operating voltage of 2-wire Tx 

10.0

Maximum voltage drop caused by controller 

5.0

Maximum voltage droop caused by indicator  1.1
Maximum voltage drop caused by cables 

0.4

                                                                             ______

16.5V

Therefore at 20mA the power supply in this
example must have an output greater than 16.5V

3.2 Remote indication

BA527C and BA528C indicators may be driven
from any 4/20mA signal to provide a remote
indication. Fig 3 shows a typical application in
which the output from a gas analyser drives a
BA527C or BA528C indicator. Again it is necessary
to ensure that the voltage capability of the 4/20mA
output is greater than the sum of the voltage drops
caused by the indicator and the cable resistance

Fig 3 Remote indication

4.  Installation

4.1 Location

BA527C and BA528C indicators are housed in
robust aluminium enclosures with polyester front
panels and Noryl bezels. The fronts of both
instruments have IP65 protection, and a gasket
seals the joint between the instrument enclosure
and the panel. The indicators may be installed in
any panel providing the environmental limits shown
in the specification are not exceeded.

Figs 4A and 4B show the overall dimensions of
each instrument and the required panel cut-out
dimensions. To achieve an IP65 seal between the
instrument enclosure and the instrument panel the
smaller tolerance aperture must be used, and the
BA528C must be secured with four mounting clips.

Содержание BA527C

Страница 1: ...Issue 3 5th March 2009 BA527C BA528C loop powered 4 digit panel mounting indicators Issue 3...

Страница 2: ...urce 6 2 Using the internal calibrator 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comme...

Страница 3: ...o the 4 20mA input current provides the input signal for the analogue to digital converter Fig 1 Simplified block diagram Each time a 4 20mA current is applied to the instrument initialisation is perf...

Страница 4: ...any 4 20mA signal to provide a remote indication Fig 3 shows a typical application in which the output from a gas analyser drives a BA527C or BA528C indicator Again it is necessary to ensure that the...

Страница 5: ...trument and tighten until the indicator is secure as shown in Fig 5 Four clips are required to achieve an IP65 between a BA528C and the instrument panel Fig 4B BA528C dimensions c Connect the panel wi...

Страница 6: ...this manual push buttons are shown in italics e g P or Up push button and legends displayed by the indicator are shown within inverted commas e g CAL and ALr2 Access to the programme menu is obtained...

Страница 7: ...0mA loop See section 5 6 Display Description of function Cond Indicator conditioning This function provides access to a sub menu enabling the internal references to be calibrated and the mains line fr...

Страница 8: ...8...

Страница 9: ...adjusted press E to enter the new zero The indicator will display Ent for a few seconds while the information is being stored in memory and will then return to the ZErO prompt To adjust the display at...

Страница 10: ...alibrator to 20 000mA and again press P The indicator will display Ent when the 20mA reference has been updated and will then return to the 020A prompt Two operations of the E button will return the i...

Страница 11: ...requency of the mains supply is 50Hz and the existing security code is 1209 In the operating mode the indicator is required to display the input current as a percentage of span when the P push button...

Страница 12: ...ain menu Step 8 Return to the display mode Return to the display mode by pressing E 6 2 Using the internal calibrator As in 6 1 the BA527C is required to display 50 0 with a 4mA input 1050 0 with a 20...

Страница 13: ...ing If a BA527C or BA528C fails to function during commissioning the following procedure should be followed Symptom Cause Solution No display Incorrect There should be 1V wiring between terminals 1 3...

Страница 14: ...d 7 6 Customer comments BEKA associates is always pleased to receive comments from customers about our products and services All communications are acknowledged and whenever possible suggestions are i...

Страница 15: ...application of alarms Summary of programmable alarm functions Display Description of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section...

Страница 16: ...y pressing the Up or Down button followed by the E button to return to the alarm menu 8 3 7 Hysteresis HStr During programming hysteresis is shown in the units the indicator has been calibrated to dis...

Страница 17: ...security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with this function disabled and the security code set to...

Страница 18: ...18 Fig 12 Alarm programme menu...

Страница 19: ...these functions the indicator initially displays the current break point and the total number of break points being used e g 5 13 current total number of break point break points Add Add a break point...

Страница 20: ...ak points Each subsequent operation of the P push button will introduce an additional break point When adding a break point to a calibrated indicator the insertion position can be selected using the U...

Страница 21: ...21...

Страница 22: ...tivated The tare function allows an operator to quickly zero the indicator display at any input current so that subsequent readings only show the change in input since the P push button was operated W...

Отзывы: