13
Step 5
Position dummy decimal point
Select 'd.P' from the main menu and
then press
P
. Using the
Up
and
Down
push-buttons position the dummy
decimal point in front of the least
significant digit.
Press
E
to return to the main menu.
Step 6
Calibrate display
With any input current between 4 and
20mA select 'SEt' from the main menu
and press
P
. The indicator will display
'ZErO' in the sub-menu, press
P
to
reveal the existing zero display. Using
the
Up
,
Down
and
P
push-buttons
enter the required zero display of
-50.0
Press
E
to return to the 'ZErO' prompt.
With any input current between 4 and
20mA press the Up push-button and
the indicator will display 'SPAn'. Press
P
to reveal the existing span display.
Using the
Up
,
Down
and
P
push-
buttons enter the required span
display of 1050.0 Press
E
to return to
the 'SPAn' prompt.
Press
E
again to return to the main
menu.
Step 7
Return to display mode
Return to the display mode by
pressing
'E'
.
7. Maintenance
7.1 Fault finding during commissioning
If a BA527C or BA528C fails to function during
commissioning the following procedure should be
followed:
Symptom
Cause
Solution
No display
Incorrect
There should be 1V
wiring
between terminals 1 &
3 with terminal 1
positive.
No display,
Incorrect
Check that a current
and 0V
wiring or
is flowing in the loop.
between
no power
terminals
supply.
1 and 3.
Insufficient
Check supply voltage
loop voltage
and voltage drops
to operate
caused by all
indicator
components in the loop.
Indicator
Positive
The indicator has been
displays 1
over-range
incorrectly calibrated &
is trying to display a
number greater than
19999.
Indicator
Negative
The indicator has been
displays –1
0ver-range
incorrectly calibrated &
is trying to display a
number less than
-19999.
Unstable
4/20mA input
Check loop supply
display
has a large
voltage.
ripple content.
Unable to
Incorrect
Enter correct security
enter the
security
code or fit security
programme
code
link in override position.
mode
entered.
See Fig 7.
7.2 Fault finding after commissioning
ENSURE PLANT SAFETY BEFORE
STARTING MAINTENANCE
If a BA527C or BA528C fails after it has been
functioning correctly, the following procedure
should be followed:
Содержание BA527C